7/26/05
888-2523-001
2-7
WARNING: Disconnect primary power prior to servicing.
Section 2 Installation / Initial Turn-On
ATLAS Analogue
a.
Lift the unit into a horizontal position using manufacturer’s recommended lifting
points
b.
Install the leg channels and brace angles
c.
Carefully place assembled unit onto concrete pad
d.
Fasten unit to the concrete pad
Install safety warning labels. Locate and install according to included instructions.
Install all supply and return plumbing. Carefully place and solder or clamp all pipe,
valves, plugs, meters, elbows, adapters, and hose, to the transmitter, pump module, heat
exchanger, reject and test loads according to the drawings (see Appendix "B.2
Plumbing System Installation" section for this step).
Mount the cooling control panel. The cooling control panel should be mounted to a
solid surface or structure (such as the Pump Module housing) so it is able to withstand
the minor vibrations of contactor operation without coming loose.
Connect conduit and route AC cabling to control panel for AC mains supply.
Install and wire according to diagram and local wiring codes.
Connect one conduit from the control panel to the pump module, and one from the
control panel to the heat exchanger, for AC wiring. Install and wire according to
diagram and local wiring codes.
Connect one conduit from the control panel to the pump module, and one from the
control panel to the heat exchanger, for status and control cable. Install and wire
according to diagram and local wiring codes.
!
CAUTION:
THE SMALL SIGNAL WIRES AND THE AC WIRING SHOULD NEVER BE RUN IN THE
SAME CONDUIT.
Open (OFF) all Isolator switches on the cooling control panel, pump module and
heat exchanger. This will allow them to be closed (ON) one at a time later to check for
wiring problems.
Содержание ATLAS ANALOGUE
Страница 4: ...iv 888 2523 001 7 26 05 WARNING Disconnect primary power prior to servicing...
Страница 6: ...vi 888 2523 001 7 26 05 WARNING Disconnect primary power prior to servicing...
Страница 8: ...viii 888 2523 001 7 26 05 WARNING Disconnect primary power prior to servicing...
Страница 10: ...x 888 2523 001 7 26 05 WARNING Disconnect primary power prior to servicing...
Страница 14: ...Table of Contents continued 4...
Страница 114: ...3 40 888 2523 001 7 26 05 WARNING Disconnect primary power prior to servicing Section 3 Operation ATLAS Analogue...