7/26/05
888-2523-001
2-33
WARNING: Disconnect primary power prior to servicing.
Section 2 Installation / Initial Turn-On
ATLAS Analogue
2.13.1.2 Setting the Test Load Flow Switch Trip Level
Prepare to set the flow meter switch trip point. See documentation included with
flow meter for procedure details.
Adjust the test load coolant supply valve until the meter reads the correct flow rate
shown in Table 2-10, or as indicated in Layout, Liquid Cooling System drawing.
NOTE:
Adjusting the flow rate of either the test load or the transmitter will, to some
extent, have an affect on the flow rate of the other. Several iterations of adjusting
one, then the other, may be necessary to attain the exact flow rates for both.
!
CAUTION:
IN ORDER TO PROTECT THE TEST LOAD, THE LOAD FLOW INTERLOCK SWITCH
MUST BE SET TO OPEN (FAULT OFF TRANSMITTER) IF ADEQUATE COOLANT
FLOW IS NOT PROVIDED TO THE LOAD.
Check the Load interlock. Once the flow rate is correct, press OUPUT to go to the RF
Output screen. This screen displays status of the load interlock (open or closed).
Adjust the flow switch trip level until the GUI displays Load Interlock: Closed.
Verify that the flow switch operates correctly by decreasing the amount of flow
through the load. The interlock should OPEN.
NOTE:
This open interlock is designed to mute the transmitter RF while the transmitter is
operating into the test load. Patch Panel status signals will tell the Main Control-
ler to ignore this interlock if the transmitter output is currently routed into the
antenna.
Go back to the nominal flow rate recommended for the test load. The interlock
should close.
2.13.1.3 Setting the Heat Exchanger Fan Turn ON Temperatures
The two thermostats that control the heat exchanger fan turn on temperatures were
factory set for 32
o
C (Fan A) and 38
o
C (Fan B).
Содержание ATLAS ANALOGUE
Страница 4: ...iv 888 2523 001 7 26 05 WARNING Disconnect primary power prior to servicing...
Страница 6: ...vi 888 2523 001 7 26 05 WARNING Disconnect primary power prior to servicing...
Страница 8: ...viii 888 2523 001 7 26 05 WARNING Disconnect primary power prior to servicing...
Страница 10: ...x 888 2523 001 7 26 05 WARNING Disconnect primary power prior to servicing...
Страница 14: ...Table of Contents continued 4...
Страница 114: ...3 40 888 2523 001 7 26 05 WARNING Disconnect primary power prior to servicing Section 3 Operation ATLAS Analogue...