GREE Photovoltaic Direct-driven Inverter Multi VRF Units
200
■High pressure sensor is abnormal
■Detecting circuit of sensor is abnormal
Tr
oubleshooting:
2.3.4.60 “F3” Low pressure sensor error
Error display:
ODU mainboard, IDU wired controller and IDU receive light board will
display
Error judgment condition and method:
Sample the AD value of low pressure sensor through sensor detecting circuit and judge the range of
AD value; if the sampled AD value exceeds upper limit and lower limit in 30 seconds continuously, report
the error.
Possible reason
:
■Poor contact between low pressure sensor and terminal in mainboard interface
■Poor contact between low pressure sensor and pressure detection position of unit
■low pressure sensor is abnormal
■Detecting circuit of sensor is abnormal
Содержание GMV5 Series
Страница 87: ...GREE Photovoltaic Direct driven Inverter Multi VRF Units 83 GMV Y96WM C F U and GMV Y120WM C F U ...
Страница 202: ...GREE Photovoltaic Direct driven Inverter Multi VRF Units 198 Troubleshooting ...
Страница 253: ...GREE Photovoltaic Direct driven Inverter Multi VRF Units 249 Troubleshooting ...
Страница 256: ...GREE Photovoltaic Direct driven Inverter Multi VRF Units 252 Troubleshooting ...
Страница 262: ...GREE Photovoltaic Direct driven Inverter Multi VRF Units 258 Troubleshooting ...
Страница 274: ...GREE Photovoltaic Direct driven Inverter Multi VRF Units 270 2 Check oil balancer ...
Страница 277: ...GREE Photovoltaic Direct driven Inverter Multi VRF Units 273 Components of oil balance valve 2 ...
Страница 287: ...GREE Photovoltaic Direct driven Inverter Multi VRF Units 283 ...
Страница 321: ...JF00303868 ...