GREE Photovoltaic Direct-driven Inverter Multi VRF Units
47
6. Fitting pipe between manifolds
Pipe size (between two manifolds at indoor unit side) is based on the total capacity of upstream
indoor unit(s).
Total capacity of downstream indoor
unit(s) C(Btu/h)
Dimension of the pipe of indoor branch
Gas Pipe mm(in.)
Liquid Pipe mm(in.)
C≤17100
Φ12.7(1/2)
Φ6.35(1/4)
17100<C≤48500
Φ15.9(5/8)
Φ9.52(3/8)
48500<C≤72000
Φ19.05(3/4)
Φ9.52(3/8)
72000<C≤96000
Φ22.2(7/8)
Φ9.52(3/8)
96000<C≤144000
Φ28.6(1
-1/8)
Φ12.7(1/2)
144000<C≤216000
Φ28.6(1
-1/8)
Φ15.9(5/8)
216000<C≤240000
Φ34.9(1
-3/8)
Φ15
.9(5/8)
240000<C≤336000
Φ34.9(1
-3/8)
Φ19.05(3/4)
336000<C
Φ41.3(1
-5/8)
Φ19.05(3/4)
7. Fitting pipe between indoor unit and manifold
Manifold should be matched with fitting pipe of indoor unit.
Rated capacity of indoor unit
C(Btu/h)
Pipe between indoor branch and IDU
Gas Pipe mm(in.)
Liquid Pipe mm(in.)
C≤9500
Φ9.52(3/8)
Φ6.35(1/4)
9500<C≤17100
Φ12.7(1/2)
Φ6.35(1/4)
17100<C≤48500
Φ15.9(5/8)
Φ9.52(3/8)
Содержание GMV5 Series
Страница 87: ...GREE Photovoltaic Direct driven Inverter Multi VRF Units 83 GMV Y96WM C F U and GMV Y120WM C F U ...
Страница 202: ...GREE Photovoltaic Direct driven Inverter Multi VRF Units 198 Troubleshooting ...
Страница 253: ...GREE Photovoltaic Direct driven Inverter Multi VRF Units 249 Troubleshooting ...
Страница 256: ...GREE Photovoltaic Direct driven Inverter Multi VRF Units 252 Troubleshooting ...
Страница 262: ...GREE Photovoltaic Direct driven Inverter Multi VRF Units 258 Troubleshooting ...
Страница 274: ...GREE Photovoltaic Direct driven Inverter Multi VRF Units 270 2 Check oil balancer ...
Страница 277: ...GREE Photovoltaic Direct driven Inverter Multi VRF Units 273 Components of oil balance valve 2 ...
Страница 287: ...GREE Photovoltaic Direct driven Inverter Multi VRF Units 283 ...
Страница 321: ...JF00303868 ...