206
Troubleshooting:
2.3.4.66 “FA” Compressor 6 discharge temperature sensor error
Er
ror display:
ODU mainboard, IDU wired controller and IDU receive light board will
display
Error judgment condition and method:
Sample the AD value of temperature sensors through temperature sensors circuit and judge the
range of AD value; if the sampled AD value exceeds upper limit and lower limit in 30 seconds
continuously, report the error.
Possible reason
:
■Poor contact between discharge temperature sensor and terminal in mainboard interface
■Discharge temperature sensor is abnormal
■Detecting circuit is abnormal