GREE Photovoltaic Direct-driven Inverter Multi VRF Units
162
2.3.3 Poor Cooling/Heating Performance
Feedback from
user
Exception
Possible reasons
Solution
Primary reason
Secondary reason
Tertiary reason
Description Confirmation
method
Description
Confirmation
method
Description
Confirmati
on
method
Poor
heating/cooling
performance
A. When the IDU
is working in the
cooling mode
and the electronic
expansion valve
is opened to the
max., the
exhaust
temperature of
the IDU's coil is
more than 5°C
higher than the
intake
temperature; B.
when the IDU is
working in the
heating mode
and the electronic
expansion valve
is opened to
2PLS, the intake
temperature of
the IDU's coil is
more than 12°C
lower than the
saturation
temperature
corresponding to
the high
pressure;
1. The stop
valve of the
ODU is not
fully opened as
required.
——
——
——
——
Manual
check
Fully open the
stop valve.
2. The system
pipeline is
blocked.
——
2.1. The system air
pipeline is blocked.
Touch the pipe
along the flowing
direction of
refrigerant to feel
the temperature
difference. The
difference is large.
2.1.1 The block
is caused by
solder.
Cut off the
pipe and
check it.
Replace and
solder the
pipe.
2.1.2 The
pipeline is
blocked by
impurities.
Replace and
solder the
pipe.
2.2 The fluid pipe is
blocked.
Touch the pipe
along the flowing
direction of
refrigerant to feel
the temperature
difference. The
difference is large
or part of the pipe is
frosting.
——
——
Replace and
solder the
pipe.
2.4 The pipe that
connects the IDU is
blocked.
Touch the pipe
along the flowing
direction of
refrigerant to feel
the temperature
difference. The
difference is large
or part of the pipe is
frosting.
2.4.1 The block
is caused by
solder.
Cut off the
pipe and
check it.
Replace and
solder the
pipe.
2.4.2 The
pipeline is
blocked by
impurities.
Replace and
solder the
pipe.
3. The ambient
temperature
exceeds the
required
range.
——
3.1 The ambient
temperature of the
IDU that works in the
cooling mode is
higher than 32°C.
Measure the
outdoor ambient
temperature.
3.1.1 The
system has
worked for less
than 1 hour.
——
It is a normal
phenomenon.
3.1.2 An
improper system
is selected.
——
Choose
another
system with
larger power.
3.2 The outdoor
ambient temperature
in the cooling mode
is higher than 40°C.
Measure the
outdoor ambient
temperature.
——
——
It is a normal
phenomenon.
3.3 The ambient
temperature of the
IDU that works in the
heating mode is
lower than 12°C.
Measure the
outdoor ambient
temperature.
3.3.1 The
system has
worked for less
than 2 hours.
——
It is a normal
phenomenon.
3.3.2 An
improper system
is selected.
——
Choose
another
system with
larger power.
3.4 The outdoor
ambient temperature
in the heating mode
is lower than -7°C.
Measure the
outdoor ambient
temperature.
——
——
It is a normal
phenomenon.
Содержание GMV5 Series
Страница 87: ...GREE Photovoltaic Direct driven Inverter Multi VRF Units 83 GMV Y96WM C F U and GMV Y120WM C F U ...
Страница 202: ...GREE Photovoltaic Direct driven Inverter Multi VRF Units 198 Troubleshooting ...
Страница 253: ...GREE Photovoltaic Direct driven Inverter Multi VRF Units 249 Troubleshooting ...
Страница 256: ...GREE Photovoltaic Direct driven Inverter Multi VRF Units 252 Troubleshooting ...
Страница 262: ...GREE Photovoltaic Direct driven Inverter Multi VRF Units 258 Troubleshooting ...
Страница 274: ...GREE Photovoltaic Direct driven Inverter Multi VRF Units 270 2 Check oil balancer ...
Страница 277: ...GREE Photovoltaic Direct driven Inverter Multi VRF Units 273 Components of oil balance valve 2 ...
Страница 287: ...GREE Photovoltaic Direct driven Inverter Multi VRF Units 283 ...
Страница 321: ...JF00303868 ...