GREE Photovoltaic Direct-driven Inverter Multi VRF Units
29
(3) Installation space requirements for triple-module unit
Unit: mm(in.)
2. When there is wall (or similar obstruction) above the unit, keep the distance between the unit top
and the wall at least 3000mm (118-1/8in.) or above. When the unit is located in a totally open space with
no obstructions in four directions, keep the distance between the unit top and wall at least 1500mm
(59in.) or above (See Fig.1). When space is limited within 1500mm (59in.) or the unit is not set in an
open space, air outlet pipe is required to be installed in order to keep good ventilation (See Fig.2).
Unit: mm(in.)
Fig.1 Fig.2