After the compressor and oil separator are removed, check the oil quality. If oil is contaminated,
replace the compressor, oil separator, and gas/liquid separator. If oil changes to black, check the oil of
other modular units. The check method is the same as instructed above.
Note: Confirm which compressor needs to be replaced. After replacing the faulty compressor, make
sure to block all its openings with adhesive tape. They should be kept intact for further analysis.
Step 7: Check system parts
If system oil is contaminated, check unit parts, including oil separator, gas/liquid separator, and
storage tank.
1) Check oil separator
Remove the oil separator. For the removal procedure, please refer to step 4. Tilt the separator to
draw the oil out into a container. Seal the container for further factory inspection.
Содержание GMV5 Series
Страница 87: ...GREE Photovoltaic Direct driven Inverter Multi VRF Units 83 GMV Y96WM C F U and GMV Y120WM C F U ...
Страница 202: ...GREE Photovoltaic Direct driven Inverter Multi VRF Units 198 Troubleshooting ...
Страница 253: ...GREE Photovoltaic Direct driven Inverter Multi VRF Units 249 Troubleshooting ...
Страница 256: ...GREE Photovoltaic Direct driven Inverter Multi VRF Units 252 Troubleshooting ...
Страница 262: ...GREE Photovoltaic Direct driven Inverter Multi VRF Units 258 Troubleshooting ...
Страница 274: ...GREE Photovoltaic Direct driven Inverter Multi VRF Units 270 2 Check oil balancer ...
Страница 277: ...GREE Photovoltaic Direct driven Inverter Multi VRF Units 273 Components of oil balance valve 2 ...
Страница 287: ...GREE Photovoltaic Direct driven Inverter Multi VRF Units 283 ...
Страница 321: ...JF00303868 ...