GREE Photovoltaic Direct-driven Inverter Multi VRF Units
159
Fault
code
Fault
Possible reasons
Solution
Primary reason
Secondary reason
Tertiary reason
Description
Confirmation
method
Description
Confirmation method
Description
Confirmation
method
E1
High
pressure
protection
4. The pressure
sensor is faulty. ——
4.2 The high
pressure and
low pressure
sensors are
connected
reversely.
Connect the stop valve of
the module fluid pipe and
air pipe to the high and
low pressure gauges and
transform the readings
into corresponding
temperatures. Compare
them to the high- and
low-temperatures tested
by the system. If the
difference is larger than
5°C, it is exceptional.
——
——
Reconnect the high-
and low-pressure
sensors.
5. The high
pressure switch
is faulty.
E1 protection is
displayed on the
unit when it is
powered on.
5.1 The high
pressure switch
is not connected
to the main
board.
——
5.1.1 The pressure
switch is not
connected to the
main board.
——
Reconnect it.
——
5.1.2 The connect
wire between the
pressure switch and
main board is faulty.
——
Reconnect them
with the wire.
5.2 The high
pressure switch
is damaged.
——
——
——
Replace the
pressure switch.
6. The fan is not
working
properly.
A. The ODU's fan
does not work in
the cooling mode.
B. The IDU's
motor does not
work in the
heating mode.
6.1 The IDU's
fan is faulty.
Manual check
6.1.1 The power
cable connecting the
motor and main
board is loose.
Manual
check
Reconnect the
motor with the
power cable.
6.1.2 The electric
capacity is not
connected or is
damaged.
Manual
check
Connect or replace
the electric capacity.
6.1.3 The motor is
damaged.
Other
reasons
Replace the motor.
6.2 The ODU's
fan is faulty.
Manual check
6.2.1 The fan motor
is not properly
connected with the
control board of the
motor with the
power cable.
Manual
check
Reconnect it
properly.
6.2.2 The fan motor
is not properly
connected with the
control board of the
motor with the signal
feedback cable.
Manual
check
Reconnect it
properly.
6.2.3 The control
board of the fan's
motor is damaged.
Manual
check
Replace the control
board of the motor.
6.2.4 The main
board of the fan's
motor is damaged.
Other
reasons
Replace the motor.
7. Too much
refrigerant
Other reasons
Incorrect
quantity of
refrigerant is
injected.
——
——
——
Check the
necessary amount
of refrigerant and
discharge
unneeded
refrigerant slowly via
the stop valve of the
fluid pipe.
Содержание GMV5 Series
Страница 87: ...GREE Photovoltaic Direct driven Inverter Multi VRF Units 83 GMV Y96WM C F U and GMV Y120WM C F U ...
Страница 202: ...GREE Photovoltaic Direct driven Inverter Multi VRF Units 198 Troubleshooting ...
Страница 253: ...GREE Photovoltaic Direct driven Inverter Multi VRF Units 249 Troubleshooting ...
Страница 256: ...GREE Photovoltaic Direct driven Inverter Multi VRF Units 252 Troubleshooting ...
Страница 262: ...GREE Photovoltaic Direct driven Inverter Multi VRF Units 258 Troubleshooting ...
Страница 274: ...GREE Photovoltaic Direct driven Inverter Multi VRF Units 270 2 Check oil balancer ...
Страница 277: ...GREE Photovoltaic Direct driven Inverter Multi VRF Units 273 Components of oil balance valve 2 ...
Страница 287: ...GREE Photovoltaic Direct driven Inverter Multi VRF Units 283 ...
Страница 321: ...JF00303868 ...