GREE Photovoltaic Direct-driven Inverter Multi VRF Units
189
Troubleshooting:
2.3.4.49 “dA” IDU network address error
Error display:
IDU wired controller and IDU receive light board will display
Error judgment condition and method:
Through testing the IDU address chip and IP address, if address chip cannot be read, IDU IP is 0 or
IP is in conflict, report the error.
Possible reason
:
■ODU allocated address is wrong
■IDU treatment is wrong
■Address chip is abnormal
Troubleshooting:
2.3.4.50 “dH” wired controller circuit board error
Error display:
IDU wired controller and IDU receive light board will display
Error judgment condition and method:
Wired controller IIC communication is abnormal
Possible reason
:
Содержание GMV5 Series
Страница 87: ...GREE Photovoltaic Direct driven Inverter Multi VRF Units 83 GMV Y96WM C F U and GMV Y120WM C F U ...
Страница 202: ...GREE Photovoltaic Direct driven Inverter Multi VRF Units 198 Troubleshooting ...
Страница 253: ...GREE Photovoltaic Direct driven Inverter Multi VRF Units 249 Troubleshooting ...
Страница 256: ...GREE Photovoltaic Direct driven Inverter Multi VRF Units 252 Troubleshooting ...
Страница 262: ...GREE Photovoltaic Direct driven Inverter Multi VRF Units 258 Troubleshooting ...
Страница 274: ...GREE Photovoltaic Direct driven Inverter Multi VRF Units 270 2 Check oil balancer ...
Страница 277: ...GREE Photovoltaic Direct driven Inverter Multi VRF Units 273 Components of oil balance valve 2 ...
Страница 287: ...GREE Photovoltaic Direct driven Inverter Multi VRF Units 283 ...
Страница 321: ...JF00303868 ...