![Gree GMV5 Series Скачать руководство пользователя страница 158](http://html1.mh-extra.com/html/gree/gmv5-series/gmv5-series_service-manual_2260367158.webp)
GREE Photovoltaic Direct-driven Inverter Multi VRF Units
154
Fault
code
Fault
Possible reasons
Solution
P8
Compressor drive IPM
over-temperature
protection
1. The compressor drive board is
faulty;
2. Thermal gel is not applied evenly
on the IPM module;
3. The IPM module is not screwed
properly.
1. Replace the compressor drive board;
2. Apply thermal gel evenly on the IPM
module;
3. Screw the IPM module properly.
P9
Inverter compressor
out-of-step protection
The compressor drive board is faulty.
The compressor is damaged.
Replace the compressor drive board.
Replace the compressor.
PH
Compressor drive DC
bus high voltage
protection
1. Does the voltage of the input power
cable of the whole system exceed 460
V;
2. The compressor drive board is
faulty.
1. Lower the voltage of the input power
cable to the required range;
2. Replace the compressor drive board.
PL
Compressor drive DC
bus low voltage
protection
1. Is the voltage of the input power
cable of the whole system lower than
320 V;
2. The compressor drive board is
faulty.
1. Elevate the voltage of the input power
cable to the required range;
2. Replace the compressor drive board.
PC
Compressor drive
current check circuit
fault
1. The compressor drive board is
faulty.
1. Replace the compressor drive board.
PF
Compressor drive
recharging circuit fault
1. Is the voltage of the input power
cable of the whole system lower than
280 V;
2. The compressor drive board is
faulty.
1. Elevate the voltage of the input power
cable to the required range;
2. Replace the compressor drive board.
PJ
Inverter compressor
starting failure
1. The drive board is damaged;
2. The compressor's UVW cable is
not connected properly;
3. The compressor is damaged.
1. Replace the compressor drive board;
2. Reconnect the compressor's UVW
cable;
3. Replace the compressor.
C3
Communication failure
between main control
board and variable
frequency fan drive
1. The control board is powered off;
2. The fan drive board is powered off;
3. The communication cable between
the control board and fan drive board
is not connected;
4. The fan drive board's dial switch is
wrong.
1. Check the power supply of the control
board. Replace the control board if it
works properly;
2. Check the power supply of the drive
board. Replace the drive board if it works
properly;
3. Connect the main board and drive
board using the communication cable;
4. Adjust the dial switch of the fan drive
board.
H3
Fan drive module reset
protection
1. The fan drive board is faulty.
1. Replace the fan drive board.
H5
Variable frequency fan
over-current protection
1. The fan drive board's IPM module
is damaged;
2. The fan's UVW cable is not
connected properly;
3. The fan is damaged.
1. Replace the fan drive board;
2. Reconnect the fan's UVW cable;
3. Replace the fan.
H6
Fan drive IPM module
protection
1. The fan drive board's IPM module
is damaged;
2. The fan's UVW cable is not
connected properly;
3. The fan is damaged.
1. Replace the fan drive board;
2. Reconnect the fan's UVW cable;
3. Replace the fan.
H7
Fan drive temperature
sensor fault
1. The fan drive board is faulty.
1. Replace the fan drive board.
H8
Fan drive IPM
over-temperature
protection
1. The fan drive board is faulty;
2. Thermal gel is not applied evenly
on the IPM module;
3. The IPM module is not screwed
properly.
1. Replace the fan drive board;
2. Apply thermal gel evenly on the IPM
module;
3. Screw the IPM module properly.
H9
Variable frequency fan
out-of-step protection
The fan drive board is faulty.
The fan is damaged.
Replace the fan drive board.
Replace the fan.
Содержание GMV5 Series
Страница 87: ...GREE Photovoltaic Direct driven Inverter Multi VRF Units 83 GMV Y96WM C F U and GMV Y120WM C F U ...
Страница 202: ...GREE Photovoltaic Direct driven Inverter Multi VRF Units 198 Troubleshooting ...
Страница 253: ...GREE Photovoltaic Direct driven Inverter Multi VRF Units 249 Troubleshooting ...
Страница 256: ...GREE Photovoltaic Direct driven Inverter Multi VRF Units 252 Troubleshooting ...
Страница 262: ...GREE Photovoltaic Direct driven Inverter Multi VRF Units 258 Troubleshooting ...
Страница 274: ...GREE Photovoltaic Direct driven Inverter Multi VRF Units 270 2 Check oil balancer ...
Страница 277: ...GREE Photovoltaic Direct driven Inverter Multi VRF Units 273 Components of oil balance valve 2 ...
Страница 287: ...GREE Photovoltaic Direct driven Inverter Multi VRF Units 283 ...
Страница 321: ...JF00303868 ...