5-8
5-9
5.2 Overview of Function Codes
This section provides an overview of the function codes
frequently used for the AF-300 Mini series of drives.
Refer to the AF-300 Mini User’s Manual, Chapter 9
“FUNCTION CODES” for details.
F00
Data Protection
Specifies whether function code data is to be protected
from being accidentally changed by keypad operation.
If data protection is enabled (F00 = 1), the or key
operation to change data is disabled. In this case no
function code data, except F00 data, can be changed
from the keypad.
F02
Running/Stopping and Rotational Direction
Selects the source issuing a run command: keypad or
external control signal input.
– If F02 = 0, 2, or 3, the drive can run the motor using
the and keys on the built-in keypad. The motor
rotational direction can be specified in two ways,
either by control signal input (F02 = 0) or by use of
prefixed forward or reverse rotation (F02 = 2 or 3).
When F02 = 0, to specify the motor rotational direc-
tion by control signal input, assign the commands
(FWD) and (REV) to terminals [FWD] and [REV],
respectively. Turn on the (FWD) or (REV) for the
forward or reverse direction, respectively, then press
the key to run the motor.
– If F02 = 1, the drive can run the motor by control
signal inputs. To specify the motor rotational
direction, assign the commands (FWD) and (REV)
to terminals [FWD] and [REV], respectively. Turn on
(FWD) or (REV) for the forward or reverse direction,
respectively. If both of (FWD) and (REV) are turned
on simultaneously, the drive immediately deceler-
ates to stop the motor.
The table below lists the operational relationship
between function code F02 (Running/Stopping and
Rotational Direction), control signal inputs to terminals
[FWD] and [REV], and the key operation, which
determines the rotational direction.
Running/
Stopping and
Rotational
Direction
Control Signal Inputs to
Terminals [FWD] and [REV]
key on the built-in keypad
Motor rotational direction
Function code F98
(REV) command
Function code F99
(FWD) command
Function code
F02
OFF
ON
OFF
ON
OFF
ON
0
✔
—
✔
—
✔
—
Stop
✔
—
—
✔
—
✔
✔
—
—
✔
—
✔
✔
—
✔
—
—
✔
Stop
✔
—
—
✔
Forward
—
✔
✔
—
Reverse
—
✔
—
✔
Stop
1
✔
—
✔
—
Not required.
Stop
✔
—
—
✔
Forward
—
✔
✔
—
Reverse
—
✔
—
✔
Stop
StockCheck.com
Содержание Fuji Electric MICRO-SAVER AF-300
Страница 1: ...GEH 6647 AF 300 Mini Startup Guide S t o c k C h e c k c o m ...
Страница 20: ...1 4 Notes S t o c k C h e c k c o m ...
Страница 36: ...2 16 Notes S t o c k C h e c k c o m ...
Страница 56: ...3 20 Notes S t o c k C h e c k c o m ...
Страница 102: ...7 8 Notes S t o c k C h e c k c o m ...
Страница 112: ...8 10 8 4 External Dimensions See dimensions table on next page S t o c k C h e c k c o m ...
Страница 118: ...8 16 Notes S t o c k C h e c k c o m ...
Страница 126: ...10 4 Notes S t o c k C h e c k c o m ...