vi
vii
Conformity to the Low Voltage Directive in the EU (continued)
CAUTION
9. Use wires listed in EN60204 Appendix C
Power supply voltage
Applicable
motor
rating (Hp)
Drive
Hp
Rated current (A) of MCCB
or RCD/ELCB *1
Main power circuit input
[L1/R, L2/S & L3/T] [L1/L
and L2/N] Grounding [G] *2
Recommended wire size
(mm2)
Drive
output [U,
V and W]
*2
DCR [P1
and P (+)]
Braking
resistor [P
(+) and DB]
*2
Control
circuit
w/ DCR
w/o DCR *3
w/ DCR
w/o DCR *3
3-phase 230 V
1/8
1/8
6
6
2.5
2.5
2.5
2.5
0.5
1/4
1/4
1/2
1/2
1
1
10
2
2
10
16
3
3
20
5
5
20
35
4
4
3-phase 460 V
1/2
1/2
6
6
2.5
2.5
2.5
2.5
0.5
1
1
2
2
10
3
3
10
16
5
5
20
1-phase 230 V
1/8
1/8
6
6
2.5
2.5
2.5
2.5
0.5
1/4
1/4
1/2
1/2
10
1
1
10
16
2
2
16
20
4
3
3
20
35
4
6
4
MCCB: Molded case circuit breaker
RDC: Residual-current-operated protective device
ELCB: Earth leakage circuit breaker
*1 The frame size and model of the MCCB or RCD/ELCB (with the exception of those exclusively designed for
protection from ground faults) will vary, depending on the power transformer capacity. Refer to the related
technical documentation for details.
*2 The above wire size for main circuits is recommended for the 70° C 600V PVC wires used at an ambient
temperature of 40°C.
*3 Wire sizes are calculated on the basis of the input current under the condition that the power supply capacity
and impedance are 500 kVA and 5%, respectively.
StockCheck.com
Содержание Fuji Electric MICRO-SAVER AF-300
Страница 1: ...GEH 6647 AF 300 Mini Startup Guide S t o c k C h e c k c o m ...
Страница 20: ...1 4 Notes S t o c k C h e c k c o m ...
Страница 36: ...2 16 Notes S t o c k C h e c k c o m ...
Страница 56: ...3 20 Notes S t o c k C h e c k c o m ...
Страница 102: ...7 8 Notes S t o c k C h e c k c o m ...
Страница 112: ...8 10 8 4 External Dimensions See dimensions table on next page S t o c k C h e c k c o m ...
Страница 118: ...8 16 Notes S t o c k C h e c k c o m ...
Страница 126: ...10 4 Notes S t o c k C h e c k c o m ...