H71
See Note2.
H80
Current oscillation suppression
gain
0.00 to 0.20
0.01
-
Y
0.20
H95
See Note2.
H96
STOP key priority / Start check
function
Data 0 1 2 3
STOP key priority function OFF ON OFF ON
Start check function OFF OFF ON ON
-
-
Y
3
H97
Clear alram data
Returns to zero after data clear by H97 setting at 1.
-
-
Y
-
H98
Protection/
(Select)
maintenance function
Data 0 1 2 3 4 5 6 7
Carrier frequency automatic DEC function
OFF ON OFF ON OFF ON OFF ON
Input phase loss protection
OFF OFF ON ON OFF OFF ON ON
Output phase loss protection
OFF OFF OFF OFF ON ON ON ON
-
-
Y
3
J codes: Application Functions
J01
PID control
(Select) 0_Inactive
-
-
N
0
1_Process control use (Normal action)
2_Process control use (Inverse action)
J02
(Remote process command) 0_Keypad panel
-
-
N
0
1_PID process command 1
4_Communication
J03
P (gain) 0.000 to 10.000 times
0.001 Times
Y
0.100
J04
I (Integration time) 0.0 to 3600.0s
0.1
s
Y
0.0
J05
D (Differentiation time) 0.0 to 600.00s
0.01
s
Y
0.00
J06
(Feedback filter) 0.0 to 900.0s
0.1
s
Y
0.5
5-7
StockCheck.com
Содержание Fuji Electric MICRO-SAVER AF-300
Страница 1: ...GEH 6647 AF 300 Mini Startup Guide S t o c k C h e c k c o m ...
Страница 20: ...1 4 Notes S t o c k C h e c k c o m ...
Страница 36: ...2 16 Notes S t o c k C h e c k c o m ...
Страница 56: ...3 20 Notes S t o c k C h e c k c o m ...
Страница 102: ...7 8 Notes S t o c k C h e c k c o m ...
Страница 112: ...8 10 8 4 External Dimensions See dimensions table on next page S t o c k C h e c k c o m ...
Страница 118: ...8 16 Notes S t o c k C h e c k c o m ...
Страница 126: ...10 4 Notes S t o c k C h e c k c o m ...