6. Troubleshooting
6.1 Before Proceeding with Troubleshooting
WARNING
If any of the protective functions have been activated, first eliminate the cause. Then, after checking that the all run
commands are set to OFF, reset the alarm. Note that if the alarm is reset while any run commands are set to ON, the
drive may supply power to the motor and cause it to start.
Injury may occur.
– Even though the drive has interrupted power to the motor, if voltage is applied
to the main circuit power input
terminals L1/R, L2/S and L3/T (L1/L and L2/N for 1-phase voltage input), then voltage may also be present at
the drive output terminals U, V, and W.
– Some residual electric charge may remain in the intermediate dc circuit capacitor even after the power is turned
off. It may take some time until the intermediate dc circuit voltage reaches a safe level. Before touching any part
of the circuit, wait for at least five minutes after the power has been turned off, and verify that the dc voltage
between main circuit terminals P (+) and N (-) is less than 25 V using a multimeter.
Electric shock may occur.
Follow the procedure below to resolve any problems.
(1) If a connection has been performed incorrectly, refer to Chapter 2, Subsection 2.3.4 “Wiring for Main Circuit
Terminals and Ground Terminals.”
(2) Is an alarm code displayed on the LED monitor?
Quick reference table of alarm codes
Alarm
code
Name
Refer
to
Alarm
code
Name
Refer
to
OC1
Overcurrent protection
p.6-10
OH4
PTC thermistor for motor protection
p.6-15
OC2
dbH
Overheat protection for braking resistor
p.6-16
OC3
OL1
Electronic thermal overload relay
p.6-17
OU1
Overvoltage protection
p.6-11
OLU
Overload protection
p.6-17
OU2
Er1
Memory error
p.6-18
OU3
Er2
Remote keypad communications error
p.6-19
LU
Undervolatge protection
p.6-12
Er3
CPU error
p.6-19
L
Input phase loss protection
p.6-13
Er6
Operation protection
p.6-20
OPL
Output phase loss protection
p.6-13
Er8
RS485 communications error
p.6-20
OH1
Overheat protection for heat sink
p.6-14
ErF
Data save error during undervoltage
p.6-21
OH2
External alarm input
p.6-15
StockCheck.com
Содержание Fuji Electric MICRO-SAVER AF-300
Страница 1: ...GEH 6647 AF 300 Mini Startup Guide S t o c k C h e c k c o m ...
Страница 20: ...1 4 Notes S t o c k C h e c k c o m ...
Страница 36: ...2 16 Notes S t o c k C h e c k c o m ...
Страница 56: ...3 20 Notes S t o c k C h e c k c o m ...
Страница 102: ...7 8 Notes S t o c k C h e c k c o m ...
Страница 112: ...8 10 8 4 External Dimensions See dimensions table on next page S t o c k C h e c k c o m ...
Страница 118: ...8 16 Notes S t o c k C h e c k c o m ...
Страница 126: ...10 4 Notes S t o c k C h e c k c o m ...