NOTE: If timer operation started by the terminal com-
mand (FWD) is finished and the drive decelerates the
motor to a stop, then the LED monitor displays “End”
and the monitor indication (“0” if the timer count is
selected) alternately. Turning (FWD) OFF will switch the
LED back to the monitor indication.
Refer to the AF-300 Mini User’s Manual, Chapter 4
“BLOCK DIAGRAMS FOR CONTROL LOGIC” for
details.
P02,
P03
Motor Parameter (Rated capacity and rated
current)
Set the nominal rated capacity denoted on the rating
nameplate of the motor.
P09
Motor Parameter (Slip compensation gain)
Set the gain to compensate the motor slip frequency
as a reference at 100% based on the typical slip of any
drive model. Set the compensation gain with respect to
motor speed.
Typical rated slip frequencies for 100%
Rated
capacity
(kW/hp)
Typical motors
rated in hp (Hz)
Typical motors
rated in kW
(Hz)
Other
motors (Hz)
0.06/0.1
2.50
1.77
1.77
0.1/0.12
2.50
1.77
1.77
0.2/0.25
2.50
2.33
2.33
0.4/0.5
2.50
2.40
2.40
0.75/1
2.50
2.33
2.33
1.5/2
2.50
2.00
2.00
2.2/3
1.17
1.80
1.80
3.7/5
1.50
1.93
1.93
The 230 V and 460 V series of motors share the same
data listed above.
P99
Motor Selection
In order to perform automatic control features such
as the auto torque boost/auto energy saving and slip
compensation or overload protection for the motor
(electronic thermal), the drive invokes the rated values
and properties of the motor. To match the drive proper-
ties of the drive and motor, set the motor properties to
this code and set function code H03 (Initialize data) to 2
to initialize the motor parameter. This action automati-
cally updates the data of function code P03 and the
constants used inside the drive.
When using GE standard motors, select the data listed
below according to model.
– P99 = 1 for GE standard motors
– P99 = 4 for Other motors
For motors from other manufacturers or unknown
models, set P99 to 4 (Other motors).
H04, H05 Retry (Times, latency time)
To automatically exit from the alarm status and restart
the drive, use the retry functions. The drive automatically
exits from Alarm mode and restarts without issuing a
block alarm even if it has already entered the forced
Alarm mode. If the drive has entered Alarm mode many
times in excess of the number of times specified by
function code H04, it issues a block alarm and does not
exit Alarm mode for restarting.
Listed below are the recoverable alarm statuses of the
drive.
Alarm Status
LED monitor display
Instantaneous overcurrent
protection
0C1, 0C2 or 0C3
Overvoltage protection
0U1, 0U2 or 0U3
Heat sink overheated
0H1
Motor overheated
0H4
Braking resistor
overheated
dbH
Motor overloaded
0L1
drive overloaded
0LU
• Retry times (H04)
Set the number of retry times for automatic exit from
Alarm mode. If the drive has entered Alarm mode many
times in excess of the number of times specified by the
function code, it issues a block alarm and does not exit
alarm mode for restarting.
WARNING
If the retry function has been selected, the drive may
automatically restart according to some causes after
tripping. (Design the machine so that human safety is
ensured after restarting.)
Otherwise an accident could occur.
StockCheck.com
Содержание Fuji Electric MICRO-SAVER AF-300
Страница 1: ...GEH 6647 AF 300 Mini Startup Guide S t o c k C h e c k c o m ...
Страница 20: ...1 4 Notes S t o c k C h e c k c o m ...
Страница 36: ...2 16 Notes S t o c k C h e c k c o m ...
Страница 56: ...3 20 Notes S t o c k C h e c k c o m ...
Страница 102: ...7 8 Notes S t o c k C h e c k c o m ...
Страница 112: ...8 10 8 4 External Dimensions See dimensions table on next page S t o c k C h e c k c o m ...
Страница 118: ...8 16 Notes S t o c k C h e c k c o m ...
Страница 126: ...10 4 Notes S t o c k C h e c k c o m ...