3-12
3-13
Displaying running status
To display the running status in hexadecimal format, each state has been assigned to bit 0 to 15 as listed in Table
3.6. Table 3.7 shows the relationship between each of the status assignments and the LED monitor display. Table
3.8 gives the conversion table from 4-bit binary to hexadecimal.
Table 3.7 Running Status Bit Allocation
Bit
Notation Content
15
BUSY
1 when function code data is being written
14
WR
Always 0
13
Always 0
12
RL
1 when communications is effective (when running commands and set frequency commands are issued via
communications)
11
ALM
1 when an alarm has occurred
10
DEC
1 during deceleration
9
ACC
1 during acceleration
8
IL
1 during current limitation
7
VL
1 under voltage control
6
TL
Always 0
5
NUV
1 when intermediate dc voltage has increased up to the specified level (0 when the voltage is too low)
4
BRK
Always 0
3
INT
1 when the drive output is shut down
2
EXT
1 during dc braking
1
REV
1 during running in the reverse direction
0
FWD
1 during running in the forward direction
Table 3.8 Running Status Display
LED No.
LED4
LED3
LED2
LED1
Bit
15
14 13
12
11
10
9
8
7
6
5
4
3
2
1
0
Notation
BUSY
WR
RL
ALM
DEC
ACC
IL VL TL NUV
BRK
INT
EXT
REV
FWD
Display
0
-
F
0
-
F
0
-
F
0
-
F
Input example
(binary)
1
0
0
0
0
0
1
1
0
0
1
0
0
0
0
1
On the LED monitor
8
3
2
1
StockCheck.com
Содержание Fuji Electric MICRO-SAVER AF-300
Страница 1: ...GEH 6647 AF 300 Mini Startup Guide S t o c k C h e c k c o m ...
Страница 20: ...1 4 Notes S t o c k C h e c k c o m ...
Страница 36: ...2 16 Notes S t o c k C h e c k c o m ...
Страница 56: ...3 20 Notes S t o c k C h e c k c o m ...
Страница 102: ...7 8 Notes S t o c k C h e c k c o m ...
Страница 112: ...8 10 8 4 External Dimensions See dimensions table on next page S t o c k C h e c k c o m ...
Страница 118: ...8 16 Notes S t o c k C h e c k c o m ...
Страница 126: ...10 4 Notes S t o c k C h e c k c o m ...