6-10
6-11
Possible Causes
What to Check and Suggested Measures
(4) Cyclic overload occurred. CHECK
Measure ripple wave of intermediate dc circuit voltage.
SUGGESTED ACTIONS
– If the ripple is large, raise the drive capacity
(5) 1-phase voltage was
supplied to the drive
instead of 3-phase
voltage.
CHECK
Check the drive type.
SUGGESTED ACTIONS
– Change the drive to one for 1-phase voltage input.
[5] OPL Output phase loss protection
Problem
Output phase loss occurred.
Possible Causes
What to Check and Suggested Measures
(1) Drive output wires are
broken
CHECK
Measure the output current.
SUGGESTED ACTIONS
– Replace the output wires.
(2) Open circuit in motor
windings
CHECK
Measure the output current.
SUGGESTED ACTIONS
– Replace the motor.
(3) The terminal screws for
drive output were not
tight enough.
CHECK
Check if any terminal screws have become loose.
SUGGESTED ACTIONS
– Tighten the terminal screws to the recommended torque.
(4) A 1-phase motor has
been connected
SUGGESTED ACTIONS
– 1-phase motors cannot be used. Note that the AF-300 Mini only drives 3-phase induction motors.
[6] OH1 Overheat protection for heat sink
Problem
Temperature around heat sink rose.
Possible Causes
What to Check and Suggested Measures
(1) Temperature around the
drive exceeded that of
drive specifications.
CHECK
Measure the temperature around the drive.
SUGGESTED ACTIONS
– Lower the temperature around the drive (e.g. improve control board ventilation).
– Reduce the load.
(2) Accumulated running
time of the cooling fan
exceeded the standard
period for replacement,
or the cooling fan
malfunctioned.
CHECK
Check the accumulated running time (E52 = 2). Refer to Chapter 3, Section 3.8 “Reading Maintenance
Information.”
SUGGESTED ACTIONS
– Replace the cooling fan.
CHECK
Visually check that the cooling fan rotates normally.
SUGGESTED ACTIONS
– Replace the cooling fan.
(3) Air vent is blocked.
CHECK
Check if there is sufficient clearance around the drive.
SUGGESTED ACTIONS
– Increase the clearance.
CHECK
Check if the heat sink is clogged.
SUGGESTED ACTIONS
– Clean the heat sink.
StockCheck.com
Содержание Fuji Electric MICRO-SAVER AF-300
Страница 1: ...GEH 6647 AF 300 Mini Startup Guide S t o c k C h e c k c o m ...
Страница 20: ...1 4 Notes S t o c k C h e c k c o m ...
Страница 36: ...2 16 Notes S t o c k C h e c k c o m ...
Страница 56: ...3 20 Notes S t o c k C h e c k c o m ...
Страница 102: ...7 8 Notes S t o c k C h e c k c o m ...
Страница 112: ...8 10 8 4 External Dimensions See dimensions table on next page S t o c k C h e c k c o m ...
Страница 118: ...8 16 Notes S t o c k C h e c k c o m ...
Страница 126: ...10 4 Notes S t o c k C h e c k c o m ...