5-2
5-3
F31
FMA Terminal
(Function)
Selects from the following items by code.
0_Output frequency (Before slip compensation)
1_Output frequency (After slip compensation)
2_Output current
3_Output voltage
6_Input power
7_PID feedback value
9_DC link circuit voltage
14_Analog output test (+)
-
-
Y
0
F37
Load select/Auto torque
boost/Energy-saving operation
0_Variable torque load
1_Constant torque load
2_Automatic torque boost
3_Energy-saving operation (Variable torque load during
ACC/DEC.)
4_Energy-saving operation (Constant torque load during
ACC/DEC.)
5_Energy-saving operation (Automatic torque boost
ACC/DEC.
-
-
N
1
F43
Current limiting 1
(Mode)
(Level)
0_Inactive
1_At constant speed
2_During acceleration and at constant speed
20 to 200%
-
-
Y
0
F44
1
%
Y
200
F50
Electronic thermal overload
(Discharge capability)
relay (for braking resistor)
(Allowable loss)
0 Internal braking resistor (optional)
1 to 900kWs, 999(cancel)
1
kWs
Y
999
F51
0.000(Braking resitor built-in type), 0.001 to 50.000
0.001
kW
Y
0.000
E codes: Extension Terminal
E01
X1 terminal function
(Select)
X2 terminal function
X3 terminal function
Selects from the following items by code.
0_(1000)Multistep freq. selection (0 to 7 stage)_SS1_
1_(1001)Multistep freq. selection (0 to 7 stage)_SS2_
2_(1002)Multistep freq. selection (0 to 7 stage)_SS4_
4_(1004)ACC/DEC time selection (2 stages) _RT1_
6_(1006)3-wire operation stop command_HLD_
7_(1007)Coast-to-stop command_BX_
8_(1008)Alarm reset_RST_
9_(1009)Trip command (External fault)_THR_
10_(1010)Jogging operation_JOG_
11_(1011)Freq. set 2 / Freq. set 1_Hz2/Hz1_
19_(1019)Write enable for Keypad (Data changeable)
_WE-KP_
20_(1020)PID control cancel_Hz/PID_
21_(1021)Normal/Inverse mode changeover_IVS_
24_(1024)Link enable (RS485 (standard), BUS (option))
_LE_
33_(1033)PID integration/differentiation reset_PID-RST_
34_(1034)PID integration hold_PID-HLD_
_The number in ( ) indicates logical inverse. (OFF when
short-circuited)
_POT/External singal input can be changed over by
Hz2/Hz1.
N
0
E02
N
7
E03
N
8
E10
Acceleration time 2
0.00 to 3600s
0.01
s
Y
6.00
E11
Deceleration time 2
0.00 to 3600s
0.01
s
Y
6.00
E20
Y1 terminal function
(Select) Selects from the following items by code.
-
-
N
0
StockCheck.com
Содержание Fuji Electric MICRO-SAVER AF-300
Страница 1: ...GEH 6647 AF 300 Mini Startup Guide S t o c k C h e c k c o m ...
Страница 20: ...1 4 Notes S t o c k C h e c k c o m ...
Страница 36: ...2 16 Notes S t o c k C h e c k c o m ...
Страница 56: ...3 20 Notes S t o c k C h e c k c o m ...
Страница 102: ...7 8 Notes S t o c k C h e c k c o m ...
Страница 112: ...8 10 8 4 External Dimensions See dimensions table on next page S t o c k C h e c k c o m ...
Страница 118: ...8 16 Notes S t o c k C h e c k c o m ...
Страница 126: ...10 4 Notes S t o c k C h e c k c o m ...