![GE Fuji Electric MICRO-SAVER AF-300 Скачать руководство пользователя страница 60](http://html.mh-extra.com/html/ge/fuji-electric-micro-saver-af-300/fuji-electric-micro-saver-af-300_startup-manual_124992060.webp)
5-2
5-3
The following tables list the function codes available for the AF-300 Mini series of drives.
F codes: Fundamental Functions
Func.
code
Name
Date entry range
Min.
Unit
Change
*1)
Factory
setting
F codes:Fundamental Functions
F00
Data protection
0_Data change enable
1_Data protection
-
-
Y
0
F01
Frequency command 1
0_Keypad operation ( or key)
1_Voltage Input (Terminal 12) (0 to +10 Vdc)
2_Current Input (Terminal C1) (4 to 20mA dc)
3_Voltage Input (Terminal 12) and current Input
(Terminal C1)
4_Potentiometer on the keypad
-
-
N
4
F02
Operation method
0_Keypad operation (FWD/REV change by external
signal)
1_External signal (Digital input)
2_Keypad operation (FWD)
3_Keypad operation (REV)
-
-
N
2
F03
Maximum frequency 1
25.0 to 400.0 Hz
0.1
Hz
N
60.0
F04
Base frequency 1
25.0 to 400.0 Hz
0.1
Hz
N
60.0
F05
Rated voltage
(at Base frequency )
0V_ Voltage in proportion to power supply voltage
80 to 240V_ AVR active (115V, 230V class)
160 to 500V_ AVR active (460V class)
1
V
N
230
460
F07
Acceleration time 1
0.00 to 3600s
_ 0.00 means acceleration time ignored (External soft
start/stop)
0.01
s
Y
6.00
F08
Deceleration time 1
0.00 to 3600s
_ 0.00 means acceleration time ignored (External soft
start/stop)
0.01
s
Y
6.00
F09
Torque boost
0.0 to 20.0% (percentage against F05: Rated voltage)
_Setting becomes valid when F37 is set at 0 or 1,3,4
0.1
%
Y
F10
Electronic thermal
(Select)
overload relay
(for motor protection)
(Level)
(Thermal time constant)
1_Active (motor with self-cooled fan, standard motor)
2_Active (motor with forced-cooled fan)
0.00(Inactive),Approx. 1 to 135% of drive rated current
0.5 to 75.0min
-
-
Y
1
F11
0.01
A
Y
GE Motor
rated
F12
0.1
min
Y
5.0
F14
Restart mode after
(Select)
momentary power
failure
0_Inactive (Trip and alarm when power failure occurs.)
1_Inactive (Trip, and alarm when power recovers.)
4_Active (Restarts at output frequency on power failure
occurrence, for general load)
5_Active (Restarts at starting frequency, for low-inertia
load)
-
-
Y
0
F15
Frequency limiter
(High)
(Low)
0.0 to 400.0 Hz
0.1
Hz
Y
70.0
F16
0.0 to 400.0 Hz
0.1
Hz
Y
0.0
F18
Bias frequency (for F01)
-100.00 to 100.00%
0.01
%
Y*
0.00
F20
DC brake
(Starting freq.)
(Braking level)
(Braking time)
0.0 to 60.0 Hz
0.1
Hz
Y
0.0
F21
0 to 100%
1
%
Y
0
F22
0.00s (Inactive), 0.01 to 30.00s
0.01
s
Y
0.00
F23
Starting frequency
0.1 to 60.0 Hz
0.1
Hz
Y
1.0
F25
Stop frequency
0.1 to 60.0 Hz
0.1
Hz
Y
0.2
F26
Motor sound
(Carrier freq.)
(Sound tone)
0.75 to 15k Hz
1
_Hz
Y
2
F27
0_Level 0
1_Level 1
2_Level 2
3_Level 3
-
-
Y
0
F30
FMA Terminal
(Output gain) 0 to 200%
1
%
Y*
100
StockCheck.com
Содержание Fuji Electric MICRO-SAVER AF-300
Страница 1: ...GEH 6647 AF 300 Mini Startup Guide S t o c k C h e c k c o m ...
Страница 20: ...1 4 Notes S t o c k C h e c k c o m ...
Страница 36: ...2 16 Notes S t o c k C h e c k c o m ...
Страница 56: ...3 20 Notes S t o c k C h e c k c o m ...
Страница 102: ...7 8 Notes S t o c k C h e c k c o m ...
Страница 112: ...8 10 8 4 External Dimensions See dimensions table on next page S t o c k C h e c k c o m ...
Страница 118: ...8 16 Notes S t o c k C h e c k c o m ...
Страница 126: ...10 4 Notes S t o c k C h e c k c o m ...