2-10
2-11
Table 2.4 Continued
Classifi-
cation
Symbol
Name
Functions
Analog input
[X1]
Digital input 1
(1) The various signals such as coast-to-stop, alarm from external equipment, and mul-
tistep frequency selection can be assigned to terminals [X1] to [X3], [FWD] and [REV]
by setting function codes E01 to E03, E98, and E99. For details, refer to Chapter 5,
Section 5.2 “Overview of Function Codes.”
(2) Input mode, i.e. Sink/Source, is changeable by using the built-in jumper switch.
(3) Switches the logic value (1/0) for ON/OFF of the terminals between [X1] to [X3],
[FWD] or [REV], and [CM]. If the logic value for ON between [X1] and [CM] is 1 in
the normal logic system, for example, OFF is 1 in the negative logic system and
vice-versa.
Digital input circuit specifications
Item
Min.
Max.
Operation
voltage
(SINK)
ON
level
0V
2V
OFF
level
22V
27V
Operation
voltage
(SOURCE)
ON
level
22V
27V
OFF
level
0V
2V
Operation current at ON
(Input Voltage at 0V)
2.5 mA
5 mA
Allowable leakage current
at OFF
-
0.5 mA
[X2]
Digital input 2
[X3]
Digital input 3
[FWD]
Forward operation
command
[REV]
Reverse operation
command
[PLC]
PLC signal power
Connects to PLC output signal power supply. (Rated voltage: 24 Vdc; Maximum output
current: 50 mA)
[CM]
Digital input
common
Common terminal for digital input signals
TIP: As shown in Figure 2.15, the digital input terminals
[X1] to [X3], [FWD] and [REV] can be switched on or off
with the open collector transistor outputs by connecting
the power input (+) of the external device, such as a
PLC, to terminal [PLC] that supplies power to the device.
To do so, switch the jumper to SINK.
NOTE: Do not connect terminal [CM] of the drive to the
common terminal of a programmable controller.
NOTE: To switch terminals [X1] through [X3], [FWD] and
[REV] on or off with contact input, use reliable contacts.
Figure 2.15 External Power Supply Connection
Table 2.4 Continued
StockCheck.com
Содержание Fuji Electric MICRO-SAVER AF-300
Страница 1: ...GEH 6647 AF 300 Mini Startup Guide S t o c k C h e c k c o m ...
Страница 20: ...1 4 Notes S t o c k C h e c k c o m ...
Страница 36: ...2 16 Notes S t o c k C h e c k c o m ...
Страница 56: ...3 20 Notes S t o c k C h e c k c o m ...
Страница 102: ...7 8 Notes S t o c k C h e c k c o m ...
Страница 112: ...8 10 8 4 External Dimensions See dimensions table on next page S t o c k C h e c k c o m ...
Страница 118: ...8 16 Notes S t o c k C h e c k c o m ...
Страница 126: ...10 4 Notes S t o c k C h e c k c o m ...