8-14
8-15
Name
Description
LED
monitor
displays
Alarm
output
[30A, B, C]
Motor
pr
otection
Overload
early
warning
Outputs a preliminary alarm at a preset level before the motor is stopped by the
electronic thermal function, for the purpose of protecting the motor.
-
-
Stall prevention
Operates when the current limit is active.
–
Current limit: Operates if the current limit set in the hardware is exceeded by
the drive’s output current, avoiding tripping of the drive (during constant speed
operation or during acceleration).
-
-
External alarm input
–
Stops the motor with an alarm through the digital input signal (THR).
0H2
Yes
Alarm relay output
(for any fault)
–
The drive outputs a relay contact signal when the drive issues an alarm, and
stops the motor.
Alarm Reset: the alarm stop state is reset by pressing the key, or by the digital
input signal (RST).
Saving the alarm history and detailed data: information for the previous 4 alarms
can be saved and displayed.
-
Yes
Memory error
The drive checks memory data after power-on and when the data is written. If a
memory error is detected, the drive stops.
E 1
Yes
Remote keypad
communications error
The drive stops on detecting any communication error between the drive and the
remote keypad (option) during operation from the remote keypad.
*
If the drive detects a communication error when the remote keypad is connected
with the power on, or when the power is turned on with the remote keypad con-
nected, it displays Er2 without alarm relay output.
E 2
Yes*
CPU error
If the drive detects a CPU error caused by noise or some other factor, the drive stops.
E 3
Yes
Operation Protection
STOP key
priority
Pressing key on the keypad forces the motor to decelerate and
stop even if the drive is running by any run commands given via the
terminals or communications (link operation). After the motor stops,
the drive issues an alarm “Er6”.
E 6
Yes
Start check
function
Any run operations are prohibited, and the drive displays “Er6” on the
LED display if any run command is given when:
–
Powering up
–
Releasing an alarm ( key turned ON)
–
Link command (LE) has switched drive operations
E 6
Yes
RS485
communication error
On detecting an RS485 communication error, the drive displays the alarm code.
E 8
Yes
Data save error
during undervoltage
If the data could not be saved during activation of the undervoltage protection
function, the drive displays the alarm code.
E F
Yes
* This alarm may not be triggered, depending upon the function code data.
“---”: Not applicable
StockCheck.com
Содержание Fuji Electric MICRO-SAVER AF-300
Страница 1: ...GEH 6647 AF 300 Mini Startup Guide S t o c k C h e c k c o m ...
Страница 20: ...1 4 Notes S t o c k C h e c k c o m ...
Страница 36: ...2 16 Notes S t o c k C h e c k c o m ...
Страница 56: ...3 20 Notes S t o c k C h e c k c o m ...
Страница 102: ...7 8 Notes S t o c k C h e c k c o m ...
Страница 112: ...8 10 8 4 External Dimensions See dimensions table on next page S t o c k C h e c k c o m ...
Страница 118: ...8 16 Notes S t o c k C h e c k c o m ...
Страница 126: ...10 4 Notes S t o c k C h e c k c o m ...