35
6. Depress the nozzle plunger two times to make sure the nozzle is not plugged. Repeat if
necessary.
Nozzle plunger
CAUTION
: Make sure no personnel put their faces into the outlet air stream
7. Make sure the TankSafe™ product is spraying out of the nozzle through the side port or
through the inlet side of the unit.
Spray viewing hole
8. Wait 15 minutes, and then monitor the % lower explosive limit (LEL) at the port on the
event riser to prevent poisoning the gas meter.
• This must be done by a qualified person.
• The meter must be a calibrated gas detector meter with an internal pump suitable for
the measuring the % LEL of the fuel vapors being degassed.
• Once below 100% LEL, take LEL readings every five minutes and record them on the
NanoVapor™ data collection sheet.
9. Every 15 minutes, verify that the nozzle is spraying the TankSafe™ product into the
airstream. If it is not, depress the nozzle plunger two times. Repeat if necessary.
10. Verify every 15 minutes that the auto-drain on the air filters are working and the filters are
not full of water.
If the auto-drain is not working, unscrew the nut on the bottom of the filter, and drain out
any water. Replace the auto-drain before next use. Check filters for oil contamination.
Содержание NANOVAPOR NV-SS ST-1000
Страница 1: ...NANOVAPORTM VAPOR SUPPRESSION SYSTEM NV SS ST 1000 INSTALLATIONAND OPERATION GUIDE ...
Страница 18: ...14 Intentionally Blank ...
Страница 34: ...30 Intentionally Blank ...
Страница 40: ...36 Intentionally Blank ...
Страница 48: ...44 Time Vent Outlet LEL TANK TOP LEL TANK MIDDLE LEL TANK BOTTOM LEL ...
Страница 54: ...50 Intentionally Blank ...
Страница 59: ...Intentionally Blank ...
Страница 60: ...405758001 r1 ...