Goodrive20 Series VFD
Function parameter list
-93-
Function
code
Name
Description
Default
Modify
P10.37
Multi-step
time unit
selection
0: Second; the running time of each step is
counted in seconds;
1: Minute; the running time of each step is
counted in minutes
0
◎
P11 group Protection parameters
Function
code
Name
Description
Default Modify
P11.00
Phase
loss
protection
0x000
–0x111
Ones place:
0: Disable software input phase loss
protection
1: Enable software input phase loss protection
Tens place:
0: Disable output phase loss protection
1: Enable output phase loss protection
Hundreds place:
0: Disable hardware input phase loss
protection
1: Enable hardware input phase loss
protection
010
(2.2kW
and lower
VFDs)
○
110 (4kW
and
higher
VFDs)
P11.01
Frequenc
y drop at
transient
power-off
0: Enable
1: Disable
0
○
P11.02
Frequenc
y drop
ratio at
transient
power-off
Setting range: 0.00Hz/s
–P00.03 (max. output
frequency)
After the grid powers off, the bus voltage
drops to the frequency drop point at transient
power-off, the VFD begins to decrease the
running frequency based on P11.02, to make
the motor generate power again. The
returning power can maintain the bus voltage
to ensure a rated running of the VFD until the
VFD is powered on again.
Voltage class
220V 380V 660V
Frequency drop point
at transient power-off
240V 460V 800V
10.00
Hz/s
○