Goodrive20 Series VFD
Function parameter list
-55-
Function
code
Name
Description
Default
Modify
Of which, f
b
is the rated frequency of the
motor, corresponding to function code is
P02.02
. n is the rated rotating speed of the
motor, corresponding to function code
P02.03
. p is the number of pole pairs of the
motor. 100.0% corresponds to the rated slip
frequency
△
f of the motor.
Setting range: 0.0
–200.0%
P04.10
Low
frequency
vibration
control
factor
In the SVPWM control mode, the motor,
especially the large-power motor, may
experience current oscillation at certain
frequencies, which may cause unstable
motor running, or even VFD overcurrent.
You can adjust the two function codes
properly to eliminate such phenomenon.
Setting range of
P04.10
and
P04.11
: 0
–100
Setting range of
P04.12
: 0.00Hz
–
P00.03
(max. output frequency)
10
○
P04.11
High
frequency
vibration
control
factor
10
○
P04.12
Vibration
control
threshold
30.00Hz
○
P04.26
Energy-sav
ing run
0: Disable
1: Automatic energy-saving operation
In light-load state, the motor can adjust the
output voltage automatically to achieve
energy saving.
0
◎
P04.27
Voltage
Setting
channel
Select the output voltage setting channel at
V/F curve separation.
0: Keypad (The output voltage is determined
by
P04.28
)
1: AI1
2: AI2
3: AI3
4: HDI
5: Multi-step speed
6: PID
7: Modbus communication
8
–10: Reversed
0
○