Goodrive20 Series VFD
Communication protocol
-138-
is logic 1.
For example: when the master sends a message to the slave, requiring it to read a group of
address data of the VFD function codes, there will be following function codes:
0 0 0 0 0 0 1 1 (Hex 03H)
For normal responses, the slave responds the same codes, while for objection responses, it
will return:
1 0 0 0 0 0 1 1 (Hex 83H)
Besides the function codes modification for the objection fault, the slave will respond a byte of
abnormal code which defines the error reason.
When the master receives the response for the objection, in a typical processing, it will send
the message again or modify the corresponding order.
For example, set the "running command channel" of the VFD (
P00.01
, parameter address is
0001H) with the address of 01H to 03, the command is as following:
VFD
address
Write
command
Parameters
address
Parameters
data
CRC check
But the setting range of "running command channel" is 0
–2, if it is set to 3, because the
number is beyond the range, the VFD will return fault response message as follows.
VFD
address
CRC check
Fault code
Abnormal
response code
Abnormal response code 86H means the abnormal response to writing command 06H; the
fault code is 04H. In the table above, its name is operation failed and its meaning is that the
parameter setting in parameter writing is invalid. For example, the function input terminal
cannot be set repeatedly.
7.5 Read/Write operation example
For details about the formats of the read and write commands, see section 7.3.
7.5.1 Examples of reading command 03H
Example 1: Read the state word 1 of the VFD with the address of 01H (refer to table 1). From
the table 1, the parameter address of the state word 1 of the VFD is 2100H.