![FOTEK GD20-004G-2 Скачать руководство пользователя страница 79](http://html.mh-extra.com/html/fotek/gd20-004g-2/gd20-004g-2_operation-manual_2324086079.webp)
Goodrive20 Series VFD
Function parameter list
-74-
Function
code
Name
Description
Default
Modify
17: External fault (EF)
18: 485 communication fault (CE)
19: Current detection fault (ItE)
20: Motor autotuning fault (tE)
21: EEPROM operation fault (EEP)
22: PID feedback offline fault (PIDE)
23: Braking unit fault (bCE)
24: Running time reached (END)
25: Electronic overload (OL3)
26: Keypad communication error (PCE)
27: Parameter upload error (UPE)
28: Parameter download error (DNE)
29
–31: Reserved
32: To-ground short-circuit fault 1 (ETH1)
33: To-ground short-circuit fault 2 (ETH2)
34: Speed deviation fault (dEu)
35: Mal-adjustment fault (STo)
36: Underload fault (LL)
P07.33
Running frequency at present fault
0.00Hz
●
P07.34
Ramp reference frequency at present fault
0.00Hz
P07.35
Output voltage at present fault
0V
P07.36
Output current at present fault
0.0A
P07.37
Current bus voltage at present fault
0.0V
P07.38
Max. temperature at present fault
0.0°C
P07.39
Input terminal state at present fault
0
●
P07.40
Output terminal state at present fault
0
●
P07.41
Reference frequency at the last fault
0.00Hz
●
P07.42
Ramp reference frequency at the last fault
0.00Hz
●
P07.43
Output voltage at last fault
0V
●
P07.44
Output current at last fault
0.0A
●
P07.45
Bus voltage at last fault
0.0V
●
P07.46
Max. temperature at last fault
0.0°C
●
P07.47
Input terminal state at last fault
0
●
P07.48
Output terminal state at last fault
0
●
P07.49
Running frequency at the last but one faults
0.00Hz
●
P07.50
Ramp reference frequency at the last but one faults
0.00Hz
●
P07.51
Output voltage at the last but one faults
0V
●
P07.52
Output current at the last but one faults
0.0A
●
Содержание GD20-004G-2
Страница 1: ......
Страница 171: ...6 6 0 0 7 0 0 9 5 7 ...