Goodrive20 Series VFD
Function parameter list
-95-
Function
code
Name
Description
Default Modify
exceeds the current-limit level, the VFD will
run at stable frequency during accelerated
running, or run in decreased frequency during
constant-speed running; if it exceeds the
current-limit level continuously, the VFD
output frequency will drop continuously until
reaching lower limit frequency. When the
output current is detected to be lower than the
current-limit level again, it will continue
accelerated running.
Output current A
Output frequency f
Current-limit
threshold
Set
frequency
Acceleration
Constant
speed
Time t
Time t
Setting range of
P11.05
: 0x00
–0x12
Setting range of
P11.06
: 50.0
–200.0%
(relative to the percentage of rated current of
the VFD)
Setting range of
P11.07
: 0.00
–50.00Hz/s
P11.08
Pre-alarm
selection
for
VFD/moto
r OL/UL
Overload pre-alarm signal will be outputted if
the output current of the VFD or motor is
higher than overload pre-alarm detection level
(
P11.09
), and the duration exceeds overload
pre-alarm detection time (
P11.10
).
Y,
RO1, RO2
Output current
Overload pre-alarm
threshold
Time t
Time t
Pre-alarm time t
Pre-alarm time t
0x0000
○
P11.09
Overload
pre-alarm
detection
level
150%
○
P11.10
Overload
pre-alarm
detection
time
1.0s
○