Goodrive20 Series VFD
Optional peripheral accessories
-157-
To ensure safety, you can configure an electromagnetic contactor on the input side to control
the switch-on and switch-off of the main circuit power, so that the input power supply of the
VFD can be effectively cut off when a system fault occurs.
Model
Fuse
(A)
Breaker
(A)
Contactor rated current
(A)
GD20-0R4G-S2
10
10
9
GD20-0R7G-S2
16
16
12
GD20-1R5G-S2
25
25
25
GD20-2R2G-S2
50
40
32
GD20-0R4G-2
6
6
9
GD20-0R7G-2
10
10
9
GD20-1R5G-2
16
16
12
GD20-2R2G-2
25
25
18
GD20-004G-2
35
32
25
GD20-5R5G-2
35
32
32
GD20-7R5G-2
50
63
50
GD20-0R7G-4
6
6
9
GD20-1R5G-4
10
10
9
GD20-2R2G-4
10
10
9
GD20-004G-4
25
25
25
GD20-5R5G-4
35
32
25
GD20-7R5G-4
50
40
38
GD20-011G-4
63
63
50
GD20-015G-4
63
63
50
GD20-018G-4
100
100
65
GD20-022G-4
100
100
80
GD20-030G-4
125
125
95
GD20-037G-4
150
160
115
GD20-045G-4
150
200
170
GD20-055G-4
200
200
170
GD20-075G-4
250
250
205
GD20-090G-4
325
315
245
GD20-110G-4
350
350
300
C.5 Reactors
When the voltage of the grid is high, the transient large current that flows into the input power
circuit may damage rectifier components. You need to configure an AC reactor on the input
side, which can also improve the current adjustment coefficient on the input side.
When the distance between the VFD and motor is longer than 50 m, the parasitic capacitance