Goodrive20 Series VFD
Function parameter list
-103-
Function
code
Name
Description
Default Modify
P17.27
Simple PLC
and current
step
number of
multi-step
speed
Display simple PLC and current step number
of multi-step speed
Range: 0
–15
●
P17.28
ASR
controller
output
Displays the speed loop ASR controller
output value under vector control mode,
relative to the percentage of rated torque of
the motor.
Range:
-300.0%
–300.0% (rated motor
current)
●
P17.29
–
P17.31
Reserved
●
P17.32
Motor flux
linkage
Displays flux linkage value of the motor.
Range: 0.0%
–200.0%
●
P17.33
Exciting
current
reference
Displays the exciting current reference value
under vector control mode.
Range: -3000.0
–+3000.0A
●
P17.34
Torque
current
reference
Displays torque current reference value
under vector control mode.
Range: -3000.0
–+3000.0A
●
P17.35
AC
incoming
current
Displays the valid value of incoming current
on AC side.
Range: 0.0
–5000.0A
●
P17.36
Output
torque
Displays output torque value, positive value
is motoring state, and negative value is
generating state.
Range: -3000.0 Nm
–3000.0 Nm
●
P17.37
Motor
overload
count value
0
–100 (Display the "OL1" fault when the
count value is 100)
●
P17.38
PID output
value
Displays PID output value.
Range: -100.00
–100.00%
●
P17.39
Function
code in
parameter
download
error
0.00
–99.99
0.00
●