P01.25
0Hz
output
Select the 0Hz output of the VFD.
0: Output without voltage
1: Output with voltage
2: Output at the DC braking current
0
○
P02 group Motor 1 parameters
Function
code
Name
Description
Default
Modify
P02.01
Rated
power of
asynchrono
us motor
0.1
–3000.
0kW
Parameters of the controlled
asynchronous motor.
To ensure the control
performance, set
P02.01
–
P02.05
correctly according to the
information on the nameplate of
the asynchronous motor.
The Goodrive20 series VFD
provides the parameter
autotuning function. Whether
parameter autotuning can be
performed properly depends on
the settings of the motor
nameplate parameters.
In addition, you need to configure
a motor based on the standard
motor configuration of the VFD. If
the power of the motor is greatly
different from that of the standard
motor configuration, the control
performance of the VFD degrades
significantly.
Note:
Resetting the rated power of the
motor (
P02.01
) can initialize the
parameters of
P02.02
to
P02.10
.
Depend
on model
◎
P02.02
Rated
frequency
of
asynchrono
us motor
0.01 Hz
–
P00.03
50.00Hz
◎
P02.03
Rated
speed of
asynchrono
us motor
1
–60000
rpm
Depend
on model
◎
P02.04
Rated
voltage of
asynchrono
us motor
0
–1200V
Depend
on model
◎
P02.05
Rated
current of
asynchrono
us motor
0.8
–6000.
0A
Depend
on model
◎
P02.06
Stator
resistor of
asynchrono
us motor
0.001
–65.
535Ω
After motor parameter autotuning
is properly performed, the values
of
P02.06
to
P02.10
are
Depend
on model
○