Goodrive20 Series VFD
Function parameter list
-33-
Function
code
Name
Description
Default Modify
multi-function terminals HDI. Set
P05.00
(HDI input selection) to high speed pulse
input.
5: Simple PLC program setting
The VFD runs at simple PLC program mode
when
P00.06
=5 or
P00.07
=5. Set
P10
(simple PLC and multi-step speed control) to
select the running frequency running
direction, ACC/DEC time and the keeping
time of corresponding step. See the function
description of
P10
for detailed information.
6: Multi-step speed running setting
The VFD runs at multi-step speed mode
when
P00.06
=6 or
P00.07
=6. Set
P05
to
select the current running step, and set
P10
to select the current running frequency.
The multi-step speed has the priority when
P00.06
or
P00.07
does not equal to 6, but
the setting step can only be the 1
–15 step.
The setting step is 1
–15 if
P00.06
or
P00.07
equals to 6.
7: PID control setting
The running mode of the VFD is process PID
control when
P00.06
=7 or
P00.07
=7. It is
necessary to set
P09
. The running frequency
of the VFD is the value after PID effect. See
P09
for the detailed information of the preset
source, preset value and feedback source of
PID.
8: Modbus communication setting
The
frequency
is
set
by
Modbus
communication. See
P14
for detailed
information.
9
–11: Reserved
P00.08
B frequency
command
reference
selection
0: Maximum output frequency, 100% of B
frequency setting corresponds to the
maximum output frequency
1: A frequency command, 100% of B
frequency setting corresponds to the
0
○