Fault code
Fault type
Possible cause
Solutions
protection is not open.
related function codes.
UV
Bus undervoltage
The voltage of the power
supply is too low.
Check the input power of
the supply line.
OL1
Motor overload
The voltage of the power
supply is too low;
The motor setting rated
current is incorrect;
The motor stall or load
transients is too strong.
Check the power of the
supply line;
Reset the rated current of
the motor;
Check the load and
adjust the torque lift.
OL2
VFD overload
The acceleration is too
fast;
Reset the rotating motor;
The voltage of the power
supply is too low;
The load is too heavy;
The motor power is too
large, and the power of
the VFD is too small.
Increase the ACC time;
Avoid the restarting after
stopping;
Check the power of the
supply line;
Select a VFD with bigger
power;
Select a proper motor.
SPI
Phase loss on
input side
Phase loss or violent
fluctuation occurred to R,
S, and T input.
Check input power;
Check installation
distribution.
SPO
Phase loss on
output side
Phase loss occurred to
U, V, W output (or the
three phases of motor is
asymmetrical)
Check the output
distribution;
Check the motor and
cable.
OH1
Rectifier module
overheat
Air duct jam or fan
damage;
Ambient temperature is
too high;
The time of overload
running is too long.
Dredge the vent duct or
replace the fan;
Lower the ambient
temperature.
OH2
Inverter module
overheat
EF
External fault
SI external fault input
terminals action
Check the external
device input
CE
485
communication
fault
The baud rate setting is
incorrect;
Fault
occurs
to
the
communication wiring;
Set proper baud rate;
Check the
communication
connection distribution;