![FOTEK GD20-004G-2 Скачать руководство пользователя страница 37](http://html.mh-extra.com/html/fotek/gd20-004g-2/gd20-004g-2_operation-manual_2324086037.webp)
Goodrive20 Series VFD
Function parameter list
-32-
Function
code
Name
Description
Default Modify
P00.07
B frequency
command
selection
0: Keypad data setting
Modify the value of function code
P00.10
(frequency set through keypad) to modify the
frequency by the keypad.
1: Analog AI1 setting (corresponding keypad
potentiometer)
2: Analog AI2 setting (corresponding terminal
AI2)
3: Analog AI3 setting (corresponding terminal
AI3)
Set the frequency by analog input terminals.
Goodrive20 series VFDs provide 3 channels
analog input terminals as the standard
configuration, of which AI1 is adjusting
through analog potentiometer, while AI2 is
the voltage/current option (0
–10V/0–20mA)
which can be shifted by jumpers; while AI3 is
voltage input (-10V
–+10V).
Note:
when analog AI2 select 0
–20 mA
input, the corresponding voltage of 20mA is
10V.
100.0%
of
the
analog
input
setting
corresponds to the maximum frequency
(function code
P00.03
) in forward direction
and -100.0% corresponds to the maximum
frequency in reverse direction (function code
P00.03
)
4: High-speed pulse HDI setting
The frequency is set by high-speed pulse
terminals. Goodrive20 series VFDs provide 1
high speed pulse input as the standard
configuration. The pulse frequency range is
0.00
–50.00 kHz.
100.0% of the high speed pulse input setting
corresponds to the maximum frequency in
forward direction (function code
P00.03
) and
-100.0% corresponds to the maximum
frequency in reverse direction (function code
P00.03
).
Note:
The pulse setting can only be input by
2
○
Содержание GD20-004G-2
Страница 1: ......
Страница 171: ...6 6 0 0 7 0 0 9 5 7 ...