Goodrive20 Series VFD
Function parameter list
-97-
Function
code
Name
Description
Default Modify
time
Setting range of
P11.12
: 0.1
–3600.0s
P11.13
Fault
output
terminal
action
upon fault
occurring
The function code is used to set the action of
fault output terminals at undervoltage and fault
reset.
0x00
–0x11
Ones place:
0: Act at undervoltage
1: Do not act at undervoltage
Tens place:
0: Act at fault reset
1: Do not act at fault reset
0x00
○
P11.16
Extensio
n
function
selectio
n
0x00
–0x11
Ones place: Automatic frequency drop
selection at voltage drop
0: Disable
1: Enable
Tens place: Second ACC/DEC time selection
0: Disable
1: Enable. When the running frequency
exceeds
P08.36
, ACC/DEC time is switched
to the second ACC/DEC time.
0x00
○
P13 group SM control
Function
code
Name
Description
Default Modify
P13.09
Frequency
switching
point
0.00~630.00
50.00
○
P13.13
Short-circuit
braking
current
When the VFD starts in direct start mode
(
P01.00
=0), set
P13.14
to a non-zero
value to enter short-circuit braking.
During stop, if the running frequency of
VFD is lower than the starting frequency
P01.09
of brake for stop, set
P13.15
to a
non-zero value to enter short-circuit
braking for stop, and then carry out DC
braking in the time set by
P01.12
. (Refer
to the descriptions for
P01.09
–
P01.12
.)
Setting range of
P13.13
: 0.0
–150.0%
0.0%
○
P13.14
Hold time of
short-circuit
braking for
start
0.00s
○
P13.15
Hold time of
short-circuit
braking for
stop
0.00s
○