Goodrive20 Series VFD
Function parameter list
-87-
Function
code
Name
Description
Default
Modify
Output frequency f
Time t
Feedback value
Deviation
limit
Reference value
Time t
Setting range: 0.0
–100.0%
P09.09
Upper limit
value of
PID output
The two function codes are used to set the
upper /lower limit value of PID regulator.
100.0%
corresponds
to
max.
output
frequency (
P00.03
) or max. output voltage
(
P04.31
).
Setting range of
P09.09
:
P09.10
–100.0%
Setting range of
P09.10
: -100.0%
–
P09.09
100.0%
○
P09.10
Lower limit
value of
PID output
0.0%
○
P09.11
Feedback
offline
detection
value
Set the PID feedback offline detection value,
when the detection value is no more than the
feedback offline detection value, and the
duration exceeds the value set in
P09.12
, the
VFD will report "PID feedback offline fault",
and keypad displays PIDE.
Time t
Output frequency f
t1
t2
P09.11
t1< t2, so the VFD continues running
t2=P09.12
Running
Fault output PIDE
PIDE
Setting range of
P09.11
: 0.0
–100.0%
Setting range of
P09.12
: 0.0
–3600.0s
0.0%
○
P09.12
Feedback
offline
detection
time
1.0s
○
P09.13
PID control
selection
0x0000
–0x1111
Ones place:
0: Continue integral control after the
frequency reaches upper/lower limit
1: Stop integral control after the frequency
reaches upper/lower limit
0x0001
○