![FOTEK GD20-004G-2 Скачать руководство пользователя страница 96](http://html.mh-extra.com/html/fotek/gd20-004g-2/gd20-004g-2_operation-manual_2324086096.webp)
Goodrive20 Series VFD
Function parameter list
-91-
Function
code
Name
Description
Default
Modify
step 8
codes of terminal 1, terminal 2, terminal 3, and
terminal 4.
The start-up and stopping of multi-step
running is determined by
P00.06
. The relation
between terminal 1, terminal 2, terminal 3,
terminal 4 and multi-step speed are as
following:
Termin
al 1
OFF ON OFF ON
OF
F
ON
OF
F
ON
Termin
al 2
OFF OFF ON ON
OF
F
OF
F
ON ON
Termin
al 3
OFF OFF OFF
OF
F
ON ON ON ON
Termin
al 4
OFF OFF OFF
OF
F
OF
F
OF
F
OF
F
OF
F
Step
0
1
2
3
4
5
6
7
Termin
al 1
OFF ON OFF ON
OF
F
ON
OF
F
ON
Termin
al 2
OFF OFF ON ON
OF
F
OF
F
ON ON
Termin
al 3
OFF OFF OFF
OF
F
ON ON ON ON
Termin
al 4
ON ON ON ON ON ON ON ON
step
8
9
10 11 12 13 14 15
Setting
range
of
P10.(2n,
1<n<17):
-100.0
–100.0%
Setting
range
of
P10.(2n+1,
1<n<17):
0.0
–6553.5 s (min)
P10.20
Multi-step
speed 9
0.0%
○
P10.21
Running
time of
step 9
0.0s
○
P10.22
Multi-step
speed 10
0.0%
○
P10.23
Running
time of
step 10
0.0s
○
P10.24
Multi-step
speed 11
0.0%
○
P10.25
Running
time of
step 11
0.0s
○
P10.26
Multi-step
speed 12
0.0%
○
P10.27
Running
time of
step 12
0.0s
○
P10.28
Multi-step
speed 13
0.0%
○
P10.29
Running
time of
step 13
0.0s
○
P10.30
Multi-step
speed 14
0.0%
○
P10.31
Running
time of
step 14
0.0s
○
P10.32
Multi-step
speed 15
0.0%
○
P10.33
Running
time of
step 15
0.0s
○
P10.34
Simple
PLC 0
–7
Below is the detailed instruction:
0x0000
○
Содержание GD20-004G-2
Страница 1: ......
Страница 171: ...6 6 0 0 7 0 0 9 5 7 ...