Goodrive20 Series VFD
Function parameter list
-34-
Function
code
Name
Description
Default Modify
maximum output frequency. Select this
setting if it needs to adjust on the base of A
frequency command.
P00.09
Combinatio
n of the
setting
source
0: A, the current frequency setting is A
frequency command
1: B, the current frequency setting is B
frequency command
2: A+B, the current frequency setting is A
frequency
command
+
B
frequency
command
3: A-B, the current frequency setting is A
frequency command - B frequency command
4: Max (A, B): The bigger one between A
frequency command and B frequency is the
set frequency.
5: Min (A, B): The lower one between A
frequency command and B frequency is the
set frequency.
Note:
The combination manner can be
shifted by
P05
(terminal function)
0
○
P00.10
Frequency
set through
keypad
When A and B frequency commands are
selected as "keypad setting", this parameter
will be the initial value of VFD reference
frequency.
Setting range: 0.00Hz
–
P00.03
(max. output
frequency)
50.00Hz
○
P00.11
ACC time 1
ACC time means the time needed if the VFD
speeds up from 0Hz to the max one
(
P00.03
).
DEC time means the time needed if the VFD
speeds down from the max output frequency
to 0Hz (
P00.03
).
Goodrive20 series VFDs have four groups of
ACC/DEC time which can be selected by
P05
. The factory default ACC/DEC time of
the VFD is the first group.
Setting range of
P00.11
and
P00.12
:
0.0
–3600.0 s
Depend
on model
○
P00.12
DEC time 1
Depend
on model
○