Goodrive20 Series VFD
Function parameter list
-40-
Function
code
Name
Description
Default Modify
ending step
of S curve
P01.08
Stop mode
0: Decelerate to stop. After a stop command
takes effect, the VFD lowers output
frequency based on the DEC mode and the
DEC time; after the frequency drop to 0Hz,
the VFD stops.
1: Coast to stop. After a stop command takes
effect, the VFD stops output immediately;
and the load coasts to stop according to
mechanical inertia.
0
○
P01.09
Starting
frequency
of DC
braking for
stop
Starting frequency of DC braking for stop:
During the deceleration to stop, the VFD
starts DC braking for stop when running
frequency reaches the starting frequency
determined by
P1.09
.
Waiting time before DC braking: The VFD
blocks the output before starting DC braking.
After this wait time, DC braking is started so
as to prevent overcurrent caused by DC
braking at high speed.
DC braking current for stop: The value of
P01.11
is the percentage of rated current of
VFD. Stronger current indicates greater DC
braking effect.
DC braking time for stop: It indicates the hold
time of DC braking. If the time is 0, DC
braking is invalid, and the VFD coasts to
stop.
P01.04
Acceleration
P13.14
P01.23
Constant speed
In running
Deceleration
P01.10
P13.15
P01.12
P01.09
Time t
Setting range of
P01.09
: 0.00Hz
–
P00.03
(max. output frequency)
Setting range of
P01.10
: 0.00
–50.00s
0.00Hz
○
P01.10
Waiting
time before
DC braking
0.00s
○
P01.11
DC braking
current for
stop
0.0%
○
P01.12
DC braking
time for
stop
0.00s
○