Goodrive20 Series VFD
Communication protocol
-131-
ASCII master command (sent from the
master to the VFD)
ASCII slave response (sent from the VFD
to the master)
"2"
"2"
Byte number
"0"
LRC CHK Hi
"E"
"4"
LRC CHK Lo
"8"
MSB of data to be
written to 0004H
LSB of data to be
written to 0004H
"1"
END Hi
CR
"3"
END Lo
LF
MSB of data to be
written to 0005H
"8"
/
/
"8"
/
/
MSB of data to be
written to 0004H
LSB of data to be
written to 0004H
"0"
/
/
"0"
/
/
MSB of data to be
written to 0005H
"3"
/
/
"2"
/
/
LRC CHK Hi
"1"
/
/
LRC CHK Lo
"7"
/
/
END Hi
CR
/
/
END Lo
LF
/
/
7.4 Data address definition
This section describes the address definition of communication data. The addresses are used
for controlling the running, obtaining the status information, and setting function parameters of
the VFD.
7.4.1 Function code address format rules
The parameter address occupies 2 bytes with the fact that the MSB is in the front and the LSB
is in the behind. The range of MSB and LSB are: MSB
—00–ffH; LSB—00–ffH. The MSB is the
group number before the radix point of the function code and the LSB is the number after the
radix point. But both the MSB and the LSB should be changed into hex. For example P05.05,
the group number before the radix point of the function code is 05, then the MSB of the
parameter is 05, the number after the radix point 05, then the LSB of the parameter is 05, then
the function code address is 0505H and the parameter address of P10.01 is 0A01H.
Function
code
Name
Description
Default
Modify
P10.00
Simple PLC
means
0: Stop after running once.
1: Run at the final value after running once.
2. Cycle running.
0
○