Goodrive20 Series VFD
Communication protocol
-127-
RTU master command
RTU slave command
START
T1-T2-T3-T4
START
T1-T2-T3-T4
ADDR
01H
ADDR
01H
CMD
08H
CMD
08H
MSB of
sub-function code
00H
MSB of
sub-function code
00H
LSB of sub-function
code
00H
LSB of
sub-function code
00H
MSB of data
12H
MSB of data
12H
LSB of data
ABH
LSB of data
ABH
LSB of CRC CHK
ADH
LSB of CRC CHK
ADH
MSB of CRC CHK
14H
MSB of CRC
CHK
14H
END
T1-T2-T3-T4
END
T1-T2-T3-T4
7.3.1.4 Command code 10H, continuous writing
Command code 10H means that if the master writes data to the VFD, the data number
depends on the "data number" in the command code. The max continuous reading number is
16.
For example, write 5000 (1388H) to 0004H of the VFD whose slave address is 02H and 50
(0032H) to 0005H, the frame structure is as follows.
The RTU request command is:
START
T1-T2-T3-T4 (time gap with a min. length of 3.5 bytes)
ADDR
02H
CMD
10H
MSB of data writing
address
00H
LSB of data writing address
04H
MSB of data quantity
00H
LSB of data quantity
02H
Byte number
04H
MSB of data in 0004H
13H
LSB of data in 0004H
88H
MSB of data in 0005H
00H
LSB of data in 0005H
32H
LSB of CRC
C5H
MSB of CRC
6EH
END
T1-T2-T3-T4 (time gap with a min. length of 3.5 bytes)