![Festo CMMS-AS-G2 Series Скачать руководство пользователя страница 58](http://html1.mh-extra.com/html/festo/cmms-as-g2-series/cmms-as-g2-series_description_2283130058.webp)
5
Commissioning and in operation
58
Festo – GDCP-CMMS-AS-G2-FW-EN – 1310NH – English
5.6
Interruption of the mains supply
5.6.1
Behaviour of the motor controller when the mains supply is interrupted
Timing diagram: interrupt mains supply
Controller enable
(DIN5)[X1.9]
Output stage enable
(DIN4)[X1.21]
Speed
Holding brake released
(BR+)[X6.2]
Controller ready for operation
(DOUT0)[X1.24]
t1
t3
t4
Start…
(DIN8)[X1.23]
Motion complete
(DOUT1)[X1.12]
Declared speed reached
1)
(DOUT2)[X1.25]
Common error
(DOUT3)[X1.13]
Mains supply
Output stage active
(DOUT… )[X1.…]
t2
1)
Only if declared speed = setpoint speed.
t1
≤
2.5 ms
t2
= … ms (FCT: dependent on the acceleration
ramp)
t3
= 60 ms
t4
≤
2.5 ms
Fig. 5.12 Timing diagram: interrupt mains supply
Содержание CMMS-AS-G2 Series
Страница 1: ...Description Functions Firmware design from 1 4 0 2 6 8026161 1310NH Motor controller CMMS AS G2 ...
Страница 173: ......