![Festo CMMS-AS-G2 Series Скачать руководство пользователя страница 56](http://html1.mh-extra.com/html/festo/cmms-as-g2-series/cmms-as-g2-series_description_2283130056.webp)
5
Commissioning and in operation
56
Festo – GDCP-CMMS-AS-G2-FW-EN – 1310NH – English
5.5.2
Behaviour of the motor controller during switch-off
Timing diagram: switch off motor controller via controller enable signal
Controller enable
(DIN5)[X1.9]
Output stage enable
(DIN4)[X1.21]
Output stage active
(DOUT… )[X1.…]
Holding brake released
(BR+)[X6.2]
Controller ready for operation
(DOUT0)[X1.4]
t2
t1
t3
t4
Speed setpoint value/actual value
Rest reached
(DOUT… )[X1.…]
Holding brake open
(mechanical)
t5
t6
t1
≤
5 ms
t2
= 0 ms…10 s (FCT: dependent on the
parametrised Quick-stop delay and
Quick-stop monitoring time of the speed
actual value)
t3
= 0…6553 ms (FCT: dependent on the
parametrised switch-off delay (brake control,
brake timing))
t4
≤
5 ms
t5
L
50…500 ms
t6
≤
5 ms
Fig. 5.10 Timing diagram: switch off motor controller via controller enable signal