Section 5. System Operation
5-3
5)
AC/LOW BATTERY LED
This LED/display indicates the current power status of the panel as follows:
ON
AC is present
OFF
No AC, running on battery backup
Slow Blink
Low-battery condition detected
6)
READY LED
This LED/display indicates that the system is ready for arming. The READY LED is common to all
BURGLARY ZONES with the following indications:
ON
System ready to be armed
OFF
System not ready to be armed
Slow Blink
Indicates Installer programming mode
Fast Blink
Alarm Memory mode
7)
[STAY] BUTTON
The [STAY] button arms the system, excluding zones programmed as Stay/AutoStay zones. This
provides exterior protection of the premises while allowing full access throughout the interior.
8)
[BYPASS] BUTTON
The [BYPASS] button is used to temporarily exclude protection to a specific zone(s).
9)
[INSTANT] BUTTON
If pressed, the [INSTANT] button allows arming the system in the INSTANT mode; with the
[STAY] button, it enables arming the system in the STAY/INSTANT mode.
NOTE: INSTANT mode is enabled in Question 11, Location 1.
10)
[CODE] BUTTON
The [CODE] button is used to allow entry into the Installer programming mode and permits the
entry of user codes.
This LED/display indicates that the system is currently armed (ON) or disarmed (OFF).
Fast Blink
Alarm mode (alarms have occurred)
Slow Blink
Unable to communicate with central station
KEYPAD AUXILIARY KEYS
Pressing the auxiliary keys (XK-108: two keys labeled P, A, or F at the same time; OMNI-LCD/XK-
7LC/OMNI-KP: 1/3, 7/9,
✱
/#) initiates a CS transmission, if programmed, of programmed functions
(e.g., PANIC, AUXILIARY, or FIRE); causes annunciation of the keypad sounder; and turns on the bell
output. The programmed functions are defined in Programming Submode 1, Questions 18 and 19.
See “Keypad Emergency Conditions” in this section for alternate auxiliary keys.
Keypad Sounder
The sounder (or loudspeaker) housed inside the keypad emits (annunciates) sounds according to the
condition of the security system.