Section 6. System Programming
6-17
Dialing Method: Select the type of dialing desired.
User Codes 4/6 digits: The system supports either 4-digit or 6-digit user codes. If this option is
selected, the system is set to use 6-digit codes. Existing 4-digit user codes will be automatically changed
to include “00” before the existing code (e.g., 1234 becomes 001234). If the system is set to 6-digit codes
and is changed to 4-digit codes, the first two digits of existing 6-digit user codes will be automatically
deleted (e.g., 123456 becomes 3456). NOTE: This question also affects the Installer Code as described
in Programming Submode 1, Question 00.
Bell/Siren Supervision – Select this option to comply with NFPA 72 requirements. If selected, the
bell/siren will be supervised for an open circuit across the alarm sounder output terminals. If a fault is
detected, the keypad will display a bell supervision condition.
Q 09, L4 —
Enter the digit for the desired options from the table below.
Test Interval by Time
L4
Entry
Disable
Every
Hour
1
Day
7
Days
27
Days
60
Days
90
Days
180
Days
0
✔
1
✔
2
✔
3
✔
4
✔
5
✔
6
✔
7
✔
Test Interval Reset by Event
9
✔
Test Interval by Time: Test reports
will be sent at the time interval
selected. The time of day that the
report is sent is defined in Question
22, Locations 1–4.
Test Interval Reset by Event: Test
reports will be sent at the time
interval selected unless an event that
caused a dialer report occurred before
the time interval expired. In this case,
no test report is sent. This cuts down
the communication traffic to the
central station.
A
✔
B
✔
UL
Must be programmed as “3” for
UL installations.
C
✔
D
✔
E
✔
QUESTION 10 OTHER SYSTEM OPTIONS
L1 L2 L3 L4
This question defines other system options. Enter the digits as follows: