![FBII OMNI-400 EU Скачать руководство пользователя страница 18](http://html1.mh-extra.com/html/fbii/omni-400-eu/omni-400-eu_installation-and-setup-manual_547062018.webp)
OMNI-400/OMNI-400EU and OMNI-600/OMNI-600EU Installation and Setup Guide
4-2
•
The zone is crossed to itself (e.g., Programming Submode 2, Question 33 is programmed as 0101 –
Zone 1 crossed to itself) and the zone has tripped 3 times within the timing period (Pulse counter).
Relay/Trigger Outputs
The system allows up to 12 programmable outputs. It provides 4 built-in triggers with the option of
adding up to two XL4705 Relay Modules (which provide up to 10 relay outputs). If the relay modules
are used, they must be enabled during programming (Submode 1, Question 09, Location 2). When using
relay modules, built-in triggers 3 and 4 no longer function as triggers, but serve as clock and data
inputs for the modules. The remaining 2 built-in triggers provide a total of up to 12 programmable
outputs. See Programming Questions 23–29 in Submode 1 for individual trigger programming options.
Each XL4705 Relay Module provides five form C relays. Each module must be assigned a unique
module address (0 or 1) using its DIP switches. The module addresses allow the system to identify the
specific relay numbers being used according to the following table:
Module
Number
Module DIP
Address
Relay
Numbers
Program
Question
1 0
1–5 Q23–25
2 1
6–10
Q25–27
Built-in triggers 1–4 are programmed in Questions 28 and 29.
NOTE: If the system uses relay modules, only triggers 1 and 2 are available.