Multi-Function Control ETMFC610
http://www.entecene.co.kr
81
EN
HANCED
TEC
HNOLOGY
7.1.3.4. Auto Battery Load Test
Place the curser on “BATT LOAD TEST” in MONITORING menu, press [ENT] button to move
into this menu.
GLOBAL SETTING / GENERAL
/
MONITORING / BATT LOAD TEST / Period
Range
0(OFF), 1 ~ 720 hour
Default
24
Step
1 hour
Set a time period for automatic battery load test.
7.1.3.5. Battery Management
Place the curser on “BATT MANAGEMENT” in MONITORING menu, press [ENT] button to
move into this menu.
The ETMFC610 has a battery management function that calculates and manages the battery
capacity using the charge time and discharge time of the set battery. However, for correct battery
capacity calculation, charge time and discharge time should be set for the installed battery.
GLOBAL SETTING / GENERAL
/
MONITORING / BATT MANAGEMENT / Function
Range
DISABLE, ENABLE
Default
DISABLE
Step
~
Set whether to monitor battery capacity.
If set to ENABLE, if the battery capacity is less than the "Alarm Level"
setting value, "BATBAD (Battery Bad)" event occurs.
GLOBAL SETTING / GENERAL
/
MONITORING / BATT MANAGEMENT / Charge Time
Range
60 ~ 6000 min.
Default
780
Step
1 min.
Sets the time at which the fully discharged battery (0%) will be fully
charged.
[BATT LOAD TEST]
>Period: 24
[0(OFF),1~720:1hr]
[BATT MANAGEMENT]
>Function: DISABLE
Charge Time: 780
Discharge Time:1440
Alarm Level: 50.00
Capacity Rst:100.00
[0(OFF),1~720:1hr]
[BATT MANAGEMENT]
>
Function: DISABLE
>Charge Time: 780
Discharge Time:1440
Alarm Level: 50.00
Capacity Rst:100.00
[60~6000:1 m]
Содержание ETMFC610
Страница 2: ......
Страница 10: ......
Страница 110: ...Multi Function Control ETMFC610 http www entecene co kr 100 ENHANCED TECHNOLOGY Figure 7 6 Tie Algorithm ...