GLOBAL SETTING/ COMMUNICATION/ EVENT&ETC / Daily Max I
Range
DISABLE, ENABLE
Default
DISABLE
Step
~
Select the [DISABLE/ENABLE] of Daily Maximum Load Current
transmission.
DISABLE :
Do not process Daily Maximum Load Current Event..
ENABLE :
Process Daily Maximum Load Current.
GLOBAL SETTING/ COMMUNICATION/ EVENT&ETC / Flt ‘I’ Evt
Range
NO, YES, 1SHOT
Default
1SHOT
Step
~
When occurring fault, set whether or not record AI point which is
related with fault such as fault current.
NO :
Do not send the all Fault Current Sequence to Event.
YES :
Send all
Fault Current Sequence to Event.
1SHOT :
Send the first Sequence Fault Current of Fault Sequence
to Event.
NOTE :
The Fault Current occurrence time of each Sequence is when it
becomes no voltage after experience the Fault Current.
GLOBAL SETTING/ COMMUNICATION/ EVENT&ETC / BI EvtBuff Size
Range
32, 64, 128, 256
Default
256
Step
~
Set the Binary Queue Size
[EVENT&ETC SETUP]
>
AEvt Method: OFF
AEvt Skip at Ft: NO
>Daily Max I:DISABLE
Flt ‘I’ Evt: 1SHOT
BI EvtBuff Size:256
[DISABLE/ENABLE]
[EVENT&ETC SETUP]
>
AEvt Method: OFF
AEvt Skip at Ft: NO
>
Daily Max I:DISABLE
>Flt ‘I’ Evt: 1SHOT
BI EvtBuff Size:256
[NO/YES/1SHOT]
[EVENT&ETC SETUP]
>
AEvt Method: OFF
AEvt Skip at Ft: NO
Daily Max I:DISABLE
>
Flt ‘I’ Evt: 1SHOT
>BI EvtBuff Size:256
[32/64/128/256]