7.1.6.4. INPUT/OUTPUT PORTS
Place the curser on “INPUT PORTS” or “OUTPUT PORTS” in PLC menu, press [ENT] button to
move into this menu.
1) INPUT DEBOUNCE
Place the curser on “INPUT DEBOUNCE” in INPUT PORTS menu, press [ENT] button to move into
this menu.
Input debounce timer is individually prepared in Control Input.
Input debounce timer sets a time to remove Chattering of INPUT signal.
In Input debounce timer, if Input A becomes 1, X time later, Output B becomes 1. If Input A is
disappeared, X time later, Output B becomes 0. Please refer to
“Figure 7-18. Input Debounce
Timer Symbol”
.
In PLC, A is IN101~IN
□
of Control Input, B is output for IN
□
.
Figure 7-18. Input Debounce Timer Symbol
GLOBAL SETTING / GENERAL / PLC / INPUT PORTS / INPUT DEBOUNCE / IN101
Range
0.005 ~ 300.000 sec
Default
0.020
Step
0.001 sec
Set an Input Debounce Time of IN101.
*. NOTE )
①
IN102 ~ IN112 and IN201 ~ IN214 are the same as IN101 above.
②
IN101 ~ IN112 are the SCADA input ports of the side panel, so the IN101 ~ IN112
A
0s
X
X
IN□
B
[OUTPUT PORTS]
>1.OUTPUT PULSETIME
[INPUT PORTS]
>1.INPUT DEBOUNCE
[INPUT DEBOUNCE]
>IN101 : 0.020
IN102 : 0.020
IN103 : 0.020
IN104 : 0.020
IN105 : 0.020
0.005~300.000:0.001s