Multi-Function Control ETMFC610
http://www.entecene.co.kr
145
EN
HANCED
TEC
HNOLOGY
GLOBAL SETTING/ COMMUNICATION/ PROTOCOLS / IEC60870-5/ IEC60870-5-104/ ASDU Addr
Range
0~65535
Default
0
Step
1
Select the Application Service Data Unit Address.
GLOBAL SETTING/ COMMUNICATION/ PROTOCOLS / IEC60870-5/ IEC60870-5-104/ Cyclic Period
Range
0(OFF), 1~60000 sec
Default
60
Step
1 sec
Select the Cyclic Period.
It is to set interval time between Point set for Cyclic.
GLOBAL SETTING/ COMMUNICATION/ PROTOCOLS / IEC60870-5/ IEC60870-5-104/ Time Out(t0)
Range
1~255 sec
Default
120
Step
1
Select the Timeout for connection establishment.
GLOBAL SETTING/ COMMUNICATION/ PROTOCOLS / IEC60870-5/ IEC60870-5-104/ Time Out(t1)
Range
1~255 sec
Default
15
Step
1
Select the Timeout for send or test APDUs.
GLOBAL SETTING/ COMMUNICATION/ PROTOCOLS / IEC60870-5/ IEC60870-5-104/ Time Out(t2)
Range
1~255 sec
Default
10
Step
1
Select the Timeout for acknowledgements in case of no data message
( t2<t1).
[IEC60870-5-104]
Function: DISABLE
>ASDU Address: 0
Cyclic Period: 60
Timeout(t0): 120
[1~65535:1]
[IEC60870-5-104]
Function: DISABLE
ASDU Address: 0
>Cyclic Period: 60
Timeout(t0): 120
[0(OFF),1~60000:1s]
[IEC60870-5-104]
Function: DISABLE
ASDU Address: 0
Cyclic Period: 60
>Timeout(t0): 120
[1~255:1s]
[IEC60870-5-104]
>Time Out(t1): 15
>
Time Out(t2): 10
Time Out(t2): 20
Event Perioid: 15
TCP Port No: 2404
[1~255:1s]
[IEC60870-5-104]
Time Out(t1): 15
>Time Out(t2): 10
Time Out(t2): 20
Event Perioid: 15
TCP Port No: 2404
[1~255:1s]
Содержание ETMFC610
Страница 2: ......
Страница 10: ......
Страница 110: ...Multi Function Control ETMFC610 http www entecene co kr 100 ENHANCED TECHNOLOGY Figure 7 6 Tie Algorithm ...